Système de sélection en ligne
Bienvenue dans notre bibliothèque complète d'instruments et de capteurs. Trouvez rapidement le produit et la solution adaptés à votre application. Commencez par une recherche ou choisissez un produit.

Technical articles are currently available in Chinese and English. English content is shown below.

← Back to knowledge hub
Selection and applications4 min readUpdated 2026-10-14

How to read accuracy, turndown and zero stability

A headline percentage may be insufficient at low flow. Compare definitions, operating ranges and test conditions.

Start an application checklist

Check what the percentage refers to

Percent of reading and percent of full scale use different reference quantities and cannot be compared directly. Look for additional fixed terms, minimum-flow conditions and fluid restrictions. Accuracy, repeatability, resolution and system uncertainty also describe different things.

Why zero stability matters at low flow

Coriolis data sheets often express zero stability in mass-flow units. At low flow, this term can become a larger proportion of the measured flow. Some manufacturers specify a low-flow calculation, but it must not be transferred to another model without verification. Turndown alone does not establish error throughout the operating range.

Compare two operating points

For illustration only, a 0.5 kg/h error term represents 0.5% of 100 kg/h and 5% of 10 kg/h. This is a ratio calculation, not a meter performance claim, and it does not replace the manufacturer's complete error model. Differences between calibration and field conditions also require assessment.

  • Request performance at minimum, normal and maximum flow.
  • Distinguish meter performance, installation effects and reference-instrument uncertainty.

Ask for evidence that supports comparison

Request performance definitions, applicable flow ranges, zero stability, fluid and temperature/pressure conditions, and calibration or verification information. For batching or commercial measurement, review the complete measurement chain and totalisation requirements. A display reading zero once is not evidence that zero stability meets a specification.

References and further reading

Coriolis application checklist

Gather fluid, flow, pressure/temperature and installation conditions to identify missing information and engineering checks.

Start an application checklist
Pas encore connecté à DOWESTON ?
Créez un compte pour commencer la sélection, consulter les prix et recevoir notre lettre d'information sur les dernières nouveautés.
Produits et services
Doweston propose une gamme de services pour vous aider à construire rapidement vos systèmes d'instrumentation automatisés. Contactez-nous pour en savoir plus.
Prêt à acheter ?
Si vous souhaitez acheter des produits,
contactez simplement notre équipe commerciale — nous serons ravis de vous aider.
Qui sommes-nous
DOWESTON fournit des solutions de mesure précises et fiables
— des produits de détection et de capteurs fiables dans tous les domaines !
Une demande de service ?
Si vous souhaitez optimiser votre production et réduire les arrêts,
nous pouvons vous aider à choisir les pièces de rechange et les services adaptés.
Modifier la configuration

Produit

Marque

Modèle

Confirmer les modifications Annuler
Votre écran est peut-être trop petit pour une navigation optimale.
Nous vous recommandons de continuer sur un ordinateur,
ou contactez immédiatement un ingénieur pour votre sélection !
Service plus rapide ? Appelez le
400-888-4436
Continuer la navigation