Système de sélection en ligne
Bienvenue dans notre bibliothèque complète d'instruments et de capteurs. Trouvez rapidement le produit et la solution adaptés à votre application. Commencez par une recherche ou choisissez un produit.

Technical articles are currently available in Chinese and English. English content is shown below.

← Back to knowledge hub
Field troubleshooting4 min readUpdated 2026-10-14

Why does the PLC value differ from the local display?

Check variable, units, range, status and timing along the signal path before changing wiring or calibration.

Start an application checklist

Compare the same quantity

The display may show mass flow while an output is assigned to volume, density or temperature. Review existing configuration records for variable, units, direction and instantaneous versus totalised quantity. kg/h and kg/min, or actual and standard volume, are not directly comparable. Time-stamp screenshots from both ends.

Review analog limits and scaling

For a 4–20 mA signal, check the transmitter's lower and upper limits and the PLC channel range. For example, if 4 mA represents 0 kg/h and 20 mA represents 1000 kg/h, 12 mA represents 500 kg/h. This illustrates linear scaling, not the site's configuration. Never assume 4 mA always means zero.

Review digital data definitions

For communications, use the correct model and firmware manual to check addresses, data types, byte/word order, units, multipliers and status bits. Do not copy register numbers from another model. Review analog fault output, communication loss and invalid-measurement status rather than treating an alarm value as normal flow.

  • Compare sample timing, refresh rate and damping at both ends.
  • Keep configuration, raw data and alarm records for an engineer.

Leave tests to authorised personnel

This page supports screen and document checks only. Loop tests, forced outputs, calibration, wiring changes and PLC program changes can affect control and interlocks; an engineer must follow site procedures. Cover opening, energised or pressurised work and hazardous-area tasks also require the applicable procedures. Do not change factors simply to make the values match.

References and further reading

Coriolis application checklist

Gather fluid, flow, pressure/temperature and installation conditions to identify missing information and engineering checks.

Start an application checklist
Pas encore connecté à DOWESTON ?
Créez un compte pour commencer la sélection, consulter les prix et recevoir notre lettre d'information sur les dernières nouveautés.
Produits et services
Doweston propose une gamme de services pour vous aider à construire rapidement vos systèmes d'instrumentation automatisés. Contactez-nous pour en savoir plus.
Prêt à acheter ?
Si vous souhaitez acheter des produits,
contactez simplement notre équipe commerciale — nous serons ravis de vous aider.
Qui sommes-nous
DOWESTON fournit des solutions de mesure précises et fiables
— des produits de détection et de capteurs fiables dans tous les domaines !
Une demande de service ?
Si vous souhaitez optimiser votre production et réduire les arrêts,
nous pouvons vous aider à choisir les pièces de rechange et les services adaptés.
Modifier la configuration

Produit

Marque

Modèle

Confirmer les modifications Annuler
Votre écran est peut-être trop petit pour une navigation optimale.
Nous vous recommandons de continuer sur un ordinateur,
ou contactez immédiatement un ingénieur pour votre sélection !
Service plus rapide ? Appelez le
400-888-4436
Continuer la navigation