La version française n’est pas encore disponible. La version complète en anglais est présentée ci-dessous.
← Retour à la base de connaissancesMicrowave level switches: 50 selection, application and maintenance questions
50 shared questions for Microwave level switches, covering selection, delivery, maintenance, common questions and evidence-based brand comparisons, with verification actions, limits and sources.
Conservez vos ressources techniques
Conservez un brouillon dans ce navigateur, puis importez-le manuellement dans votre bibliothèque après connexion.
La création de compte suit le processus habituel d’inscription et d’approbation. L’enregistrement de ressources n’ouvre pas automatiquement l’accès aux prix ni aux autres autorisations commerciales.
Shared guidance for this product family. Confirm the complete model and application; family-level guidance is not evidence of a particular product specification or approval.
Les principes généraux s’appliquent en complément de la validation du modèle. Les performances, homologations et alternatives dépendent du code de commande complet et des conditions réelles.
1What does the Microwave level switches principle establish, and what does it not establish?
A microwave barrier detects material-induced attenuation between transmitter and receiver for point or blockage indication. The principle explains signal generation; it does not establish the range, accuracy, materials or approvals of every model. Review the physical principle and the application limits separately.
Verification: Confirm "Separation and alignment" and assess "Metal walls are not transparent windows" against the actual application. Record the complete model and document revision used.
Limites d’application : Metal walls are not transparent windows
2Is the required result measured directly or calculated from other inputs?
Define the quantity to be accepted before selecting a display unit. A microwave barrier detects material-induced attenuation between transmitter and receiver for point or blockage indication. For "Separation and alignment", document output definitions and conversion or compensation conditions; displaying a value does not make it a direct measurement under all conditions.
Verification: Document the process objective, units and reference conditions. Check "Metal walls are not transparent windows" and list separate inputs and acceptance methods for calculated results.
Limites d’application : Metal walls are not transparent windows
3Which application information is needed before requesting a quotation?
Prepare at least these five input groups: Separation and alignment; Material dielectric and attenuation; Vessel wall and window materials; Dust, deposits and path obstruction; State logic and response. Mark unknown items for confirmation instead of substituting a normal point or an assumed default for all conditions.
Verification: Have process, instrumentation and purchasing roles agree the inputs, particularly "Material dielectric and attenuation". Resolve missing evidence before requesting application confirmation.
Limites d’application : Metal walls are not transparent windows
4How should the range be chosen rather than copied from a nominal equipment rating?
Select the range from actual operating conditions and permissible error, then check extremes and installation constraints. For this family: Metal walls are not transparent windows Nominal size or maximum equipment rating need not equal the useful measuring interval.
Verification: List minimum, normal, maximum and abnormal conditions. Check "Vessel wall and window materials" against the documented performance envelope.
Limites d’application : Metal walls are not transparent windows
5Can a larger turndown claim or display rescaling fix poor low-end performance?
No. Low-end usability depends on the principle, available signal and error mechanisms. Presence detection is not continuous level More display digits, software scaling or a stated turndown cannot remove the original noise or installation error.
Verification: Obtain error definitions and limits at the actual low operating point. Use "Does presence prove material flow → No. A stationary blockage can produce the same state; flow detection needs a suitable function. → Check transmitter/receiver pairing and alignment and record Dust, deposits and path obstruction" to investigate bias instead of comparing only percent-of-full-scale values.
Limites d’application : Presence detection is not continuous level
6How should compatibility with the measured object and materials be established?
Use the complete measured object and actual exposure, rather than a material name alone. Dust, deposits and path obstruction Avoid this family-specific misuse: Presence detection is not continuous level For non-wetted equipment, assess loads, target materials, signals and environmental compatibility instead.
Verification: List the actual contact or loading parts, seals, insulation and cleaning conditions. Have the responsible parties assess "A barrier switch is not a Doppler flowmeter".
Limites d’application : A barrier switch is not a Doppler flowmeter
7Why must abnormal and environmental conditions be listed separately from normal operation?
Normal measurement, temporary excursions and survival limits are different requirements. A barrier switch is not a Doppler flowmeter Start-up, cleaning, impacts, power interruption or abnormal environments can determine the necessary construction and protection.
Verification: Complete the worst-case conditions using "State logic and response" and check "Dust tolerance does not mean unlimited deposit tolerance". Separate continuous operating limits from temporary limits in the specification.
Limites d’application : Dust tolerance does not mean unlimited deposit tolerance
8Can the published instrument accuracy be used as the installed system accuracy?
Not without assessment. Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. The installed system also includes object, mounting, signal conversion, environmental and reference effects. Derived results additionally depend on the relevant input uncertainties.
Verification: Agree actual test points, installation conditions and the acceptance reference. Check "Check transmitter/receiver pairing and alignment" and document the system error or uncertainty basis.
Limites d’application : Presence detection is not continuous level
9How should response time, filtering and a stable display be balanced?
A stable indication and fast change detection involve a trade-off; filtering cannot repair incorrect installation or real process variation. Why can a full silo fail to alarm → The path may be unblocked, attenuation insufficient or output logic reversed. → Save signal strength and threshold before adjustment and record Vessel wall and window materials Review the complete chain when fast response matters, not merely the display refresh rate.
Verification: Define the shortest relevant event and acceptable delay. Check "Record clear and blocked-path response" and verify local output, display and receiving-system response using a controlled change.
Limites d’application : A barrier switch is not a Doppler flowmeter
10Which typical applications fit, and which require a specific engineering review?
Typical contexts include: Chute blockage; Silo high/low limit; Material-presence confirmation. Similar application labels do not establish equivalent conditions. In particular, assess "Dust tolerance does not mean unlimited deposit tolerance" before relying on another installation as proof.
Verification: Select the nearest application and compare "Separation and alignment" and "State logic and response". Obtain written confirmation where published application limits are exceeded.
Limites d’application : Dust tolerance does not mean unlimited deposit tolerance
11How should a complete order code be defined without unspecified standard options?
Translate required functions, performance and physical interfaces into verifiable options. Separation and alignment; Material dielectric and attenuation. Options affecting suitability or supply scope should be explicit; terms such as standard or same as existing are insufficient.
Verification: Check the complete order code and selection sheet, especially "Vessel wall and window materials". List accessories, documents, calibration and delivery boundaries separately.
Limites d’application : Metal walls are not transparent windows
12Which mounting and mechanical layout checks belong before ordering?
Check transmitter/receiver pairing and alignment The installation drawing must match the available space and process or mechanical structure. Access for fitting and servicing should be established before delivery.
Verification: Review a dimensioned, oriented site drawing. Use "Dust, deposits and path obstruction" and "A barrier switch is not a Doppler flowmeter" to confirm connections, support, removal access and safe isolation.
Limites d’application : A barrier switch is not a Doppler flowmeter
13How can supporting infrastructure prevent an instrument that fits but cannot be used?
Check window material and thickness Supporting conditions are part of the measurement system. Matching mechanical connections or signal names alone do not establish power, I/O, grounding or configuration compatibility.
Verification: Confirm "Check transmitter/receiver pairing and alignment" and "Verify output, failure state and receiving-system compatibility" against actual terminals, loops and receiving-system settings.
Limites d’application : Presence detection is not continuous level
14What is a sensible commissioning sequence before changing correction factors?
Check identity, installation and basic conditions first, then status, output and process response. Record clear and blocked-path response Preserve original evidence for unexplained anomalies instead of concealing them with zero or factor adjustments.
Verification: Record factory settings and initial status. Investigate "What should be checked for an empty-silo alarm → Check deposits, alignment and unintended obstruction before changing sensitivity. → Record clear and blocked-path response and record Material dielectric and attenuation" step by step and change parameters only after identifying the cause and using an authorised procedure.
Limites d’application : A barrier switch is not a Doppler flowmeter
15Do identical output units or interface names establish connection compatibility?
No. Establish the represented object and reference conditions: Separation and alignment. Electrical equipment also needs loop type, scaling, failure behaviour and protocol details checked. Mechanical indicators require clear boundaries between indication and remote-transmission accessories.
Verification: Check the receiving-system variable against "Separation and alignment" and verify limits, units and abnormal states with the actual equipment. Record wiring, configuration and end-to-end checks against "Check window material and thickness".
Limites d’application : Presence detection is not continuous level
16What should a calibration report contain to be relevant to the application?
Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. The report should identify the delivered instrument, measured quantity, conditions, method and results. A general conformity certificate does not establish performance for every option or operating condition.
Verification: Check serial number, points, units, reference equipment and traceability. Compare "Material dielectric and attenuation" with the calibrated conditions and agree separate acceptance where they differ.
Limites d’application : Presence detection is not continuous level
17How can delivery and site acceptance use reproducible pass criteria?
Save signal strength and threshold before adjustment Agree criteria before testing, including range, conditions, error definition and treatment of anomalies. Similar-looking readings or an unsuitable portable reference are not sufficient acceptance evidence.
Verification: Choose an appropriate reference using "Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment.". Record "Separation and alignment" and test conditions; investigate "Does presence prove material flow → No. A stationary blockage can produce the same state; flow detection needs a suitable function. → Check transmitter/receiver pairing and alignment and record Dust, deposits and path obstruction" before deciding on rework or recalibration.
Limites d’application : Presence detection is not continuous level
18What belongs in the quotation and agreement for a non-standard application?
Define why the standard supply is insufficient, the required verification and the responsible parties. Dust tolerance does not mean unlimited deposit tolerance; Dust tolerance does not mean unlimited deposit tolerance. Additional materials, construction, documents or tests depend on actual requirements.
Verification: Attach "State logic and response" and the deviations. Obtain technical confirmation, additional charges, delivery conditions and acceptance methods; unknown requirements must not be assumed satisfied.
Limites d’application : Dust tolerance does not mean unlimited deposit tolerance
19Where should investigation start when there is no valid reading or output?
What should be checked for an empty-silo alarm → Check deposits, alignment and unintended obstruction before changing sensitivity. → Record clear and blocked-path response and record Material dielectric and attenuation Distinguish the actual measured condition from device-state and readout or transmission faults. Do not immediately interpret missing data as sensor failure or a zero process value.
Verification: Under appropriate safe isolation, check "Check window material and thickness". Compare local and receiving-end status and record when the fault appeared.
Limites d’application : Metal walls are not transparent windows
20How can unstable readings be separated from genuine process variation?
Why can a full silo fail to alarm → The path may be unblocked, attenuation insufficient or output logic reversed. → Save signal strength and threshold before adjustment and record Vessel wall and window materials Compare independent process evidence and raw signals before deciding whether installation, interference or equipment is responsible. More filtering can hide a real abnormal event.
Verification: Keep conditions comparable and record correlation with process or equipment events. Check "Check transmitter/receiver pairing and alignment" and change one factor at a time.
Limites d’application : A barrier switch is not a Doppler flowmeter
21How should a persistent high or low bias be investigated before changing factors?
Does presence prove material flow → No. A stationary blockage can produce the same state; flow detection needs a suitable function. → Check transmitter/receiver pairing and alignment and record Dust, deposits and path obstruction Systematic bias can arise from units, reference conditions, configuration, installation or the reference method. An unexplained correction can move one operating-point error to other conditions.
Verification: Align quantities, time bases and units first. Review the reference using "Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment." and confirm that "Material dielectric and attenuation" matches the configuration.
Limites d’application : Presence detection is not continuous level
22When is it appropriate to adjust a drifting zero or reference position?
Does dust tolerance eliminate cleaning → No. Dense window deposits differ from airborne dust and can permanently attenuate the path. → Check window material and thickness and record State logic and response Establish a genuine, stable reference condition that meets the method requirements before considering adjustment. Some instruments have no freely adjustable site zero.
Verification: Check "Record clear and blocked-path response" and "Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment." and retain before-and-after results. If the conditions cannot be established, remove external effects or use a qualified service.
Limites d’application : A barrier switch is not a Doppler flowmeter
23Which evidence helps diagnose intermittent alarms or failures?
Should power loss mean alarm or normal → Define failure states explicitly; lost signal must not automatically mean no material. → Record clear and blocked-path response and record Separation and alignment Intermittent faults need correlated event records, not just a normal display after recovery. Review alarm settings, communication status and actual process abnormalities separately.
Verification: Retain time, status codes, raw trends and the contemporaneous "State logic and response". Compare "Check window material and thickness" and "Record clear and blocked-path response" to locate the failing link.
Limites d’application : Dust tolerance does not mean unlimited deposit tolerance
24Why should repeated failures trigger a cause review instead of another identical replacement?
Repeated failures warrant a common-cause assessment. Dust tolerance does not mean unlimited deposit tolerance If the external conditions remain unchanged, an identical construction or installation can experience the same failure again.
Verification: Summarise failed parts, service time and "State logic and response". Check "Check transmitter/receiver pairing and alignment" and "A barrier switch is not a Doppler flowmeter" and establish corrective action before selecting repair or redesign.
Limites d’application : A barrier switch is not a Doppler flowmeter
25What distinguishes a site comparison, an adjustment and a calibration?
Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. A comparison identifies differences; adjustment changes indication or parameters; calibration establishes a reference relationship under stated conditions. They are not interchangeable claims.
Verification: Define what performance and evidence must be established, using conditions relevant to "Material dielectric and attenuation". Retain original and adjusted results, references and responsibility records.
Limites d’application : Presence detection is not continuous level
26What must be checked again after replacing an instrument with the same basic model?
The same basic model does not establish identical options, software, calibration or accessories. Verify output, failure state and receiving-system compatibility; Confirm certificates, calibration and site change approval in writing. Previous system operation does not remove the need to verify a replacement.
Verification: Compare full order codes and revisions. Recheck critical points, failure states and interfaces using "Save signal strength and threshold before adjustment" before handover.
Limites d’application : Dust tolerance does not mean unlimited deposit tolerance
27Can every published maximum rating be achieved simultaneously?
No. Metal walls are not transparent windows Maximum values usually relate to particular options and conditions. Temperature, load, pressure, materials, speed or signal conditions may constrain one another.
Verification: Review "Vessel wall and window materials" and "State logic and response" together. Obtain confirmation for the combined conditions instead of assembling unrelated maxima from separate pages.
Limites d’application : Metal walls are not transparent windows
28Does a missing signal or zero indication establish that the process value is zero?
No. What should be checked for an empty-silo alarm → Check deposits, alignment and unintended obstruction before changing sensitivity. → Record clear and blocked-path response and record Material dielectric and attenuation Indication, measurement and transmission have distinct possible failure modes. Also consider "Metal walls are not transparent windows"; establish the actual process condition independently.
Verification: Check available status or failure indications and "Check transmitter/receiver pairing and alignment". For interlocks, follow the complete safety design rather than substituting a zero value for diagnosis.
Limites d’application : Metal walls are not transparent windows
29Does one acceptable test point establish compliance across the working range?
No. Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. Test points and directions must reflect the working interval, relevant error mechanisms and acceptance purpose. Multiple points, reversal or load tests depend on the method.
Verification: Define acceptance coverage against "Material dielectric and attenuation" and include critical operating points. Mark conditions outside the tests as unverified.
Limites d’application : Presence detection is not continuous level
30Are the largest range, highest accuracy class and most options always preferable?
Not necessarily. Options should serve the required objective; excess configuration can add cost, complexity or incompatibility. Presence detection is not continuous level; Presence detection is not continuous level. Establish essential requirements before comparing optional benefits.
Verification: Document the objective in "Separation and alignment" and why "Separation and alignment" is needed. Compare performance at actual working points rather than one headline metric.
Limites d’application : Presence detection is not continuous level
31Can every maintenance or recalibration interval simply be fixed at one year?
Not independently of risk and history. Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. Intervals depend on applicable law or contract, conditions, drift, maintenance and failure evidence. Generic advice cannot replace mandatory requirements.
Verification: Use "Does dust tolerance eliminate cleaning → No. Dense window deposits differ from airborne dust and can permanently attenuate the path. → Check window material and thickness and record State logic and response" and "Dust tolerance does not mean unlimited deposit tolerance" to establish and review an initial plan. Retain the justification and approval for interval changes.
Limites d’application : Dust tolerance does not mean unlimited deposit tolerance
32Can parts from different brands be mixed if their physical interfaces fit?
Physical fit is insufficient. Material dielectric and attenuation; Check transmitter/receiver pairing and alignment. Matching, materials, signals, calibration and approval boundaries can change with the combination.
Verification: Check the complete combination against "Check window material and thickness" and obtain compatibility and acceptance evidence. An unconfirmed assembly must not be described as an approved system.
Limites d’application : Presence detection is not continuous level
33Does a hazardous-area, hygienic or safety label establish suitability for that duty?
Check the exact order configuration and valid documents rather than a series name. Confirm certificates, calibration and site change approval in writing "Dust tolerance does not mean unlimited deposit tolerance" also matters; certificates, installation conditions and restrictions together define suitability.
Verification: Obtain certificate identifiers, covered models and special conditions and match them to the site. Similar names do not grant functional-safety or legal-metrology approval.
Limites d’application : Dust tolerance does not mean unlimited deposit tolerance
34What evidence makes the final result acceptable, reproducible and sustainable?
Establish the chain from quantity definition and application limits through configuration, mounting, reference and operating status. Save signal strength and threshold before adjustment A normal indication or brochure alone cannot demonstrate continuing system reliability.
Verification: Put "Separation and alignment", "Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment." and "Should power loss mean alarm or normal → Define failure states explicitly; lost signal must not automatically mean no material. → Record clear and blocked-path response and record Separation and alignment" into the technical, acceptance and maintenance records, with responsibility for reviewing excursions.
Limites d’application : Dust tolerance does not mean unlimited deposit tolerance
35Can a DOWESTON model replace an installed instrument from another brand?
Possibly, after a full configuration and application comparison. A basic model name or matching output is not proof of equivalent replacement. Separation and alignment; Material dielectric and attenuation; Check transmitter/receiver pairing and alignment. Record conclusions on material differences.
Verification: Provide the original full order code, data sheet and site conditions. Check "Verify output, failure state and receiving-system compatibility" and "Confirm certificates, calibration and site change approval in writing" and obtain the necessary test and approval evidence before replacement.
Limites d’application : Dust tolerance does not mean unlimited deposit tolerance
36Why choose DOWESTON, and what would make that reasoning evidence-based?
Base the decision on project compliance and documented delivery or service, rather than a slogan. "Separation and alignment" and "Metal walls are not transparent windows" are important family-specific checks. Claim only benefits supported by the offered product documents and written commitments.
Verification: Request the proposed configuration matching "Separation and alignment", test evidence and delivery/service terms. Do not infer unverified performance, approvals, origin or service life.
Limites d’application : Metal walls are not transparent windows
37How can competing brands be compared beyond a single accuracy or price figure?
Use identical conditions and supply boundaries. Separation and alignment; Check transmitter/receiver pairing and alignment; Confirm certificates, calibration and site change approval in writing. Quotes with different ranges, compensation, accessories or calibration scope can conceal material differences.
Verification: Compare "Material dielectric and attenuation", "Presence detection is not continuous level" and mounting/acceptance conditions. Separate demonstrated, unverified and inapplicable items; do not claim unproven overall superiority.
Limites d’application : Presence detection is not continuous level
38How should purchasing compare cost without overlooking additions or rework?
Compare complete supply and use-cycle costs, not only the main instrument price. Check transmitter/receiver pairing and alignment; Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. List the actual installation, supporting equipment, calibration, consumables, downtime and service requirements without assuming any brand is always cheaper.
Verification: Use the same "Separation and alignment" configuration and "State logic and response" boundary. Separate equipment, accessories, commissioning and maintenance responsibilities and retain a traceable comparison.
Limites d’application : Dust tolerance does not mean unlimited deposit tolerance
39Is a microwave barrier a small radar level transmitter?
No. Path attenuation indicates presence rather than continuous echo distance. Verify Check transmitter/receiver pairing and alignment and record Separation and alignment. Metal walls are not transparent windows. Confirm the exact model and record the result before changing settings.
Verification: Check transmitter/receiver pairing and alignment and record Separation and alignment
Limites d’application : Metal walls are not transparent windows
40Can it detect through a metal wall?
A suitable microwave-transparent window or process installation is required. Verify Check window material and thickness and record Material dielectric and attenuation. Presence detection is not continuous level. Confirm the exact model and record the result before changing settings.
Verification: Check window material and thickness and record Material dielectric and attenuation
Limites d’application : Presence detection is not continuous level
41Why does equal material thickness give different signal?
Moisture, density and electrical properties affect attenuation. Verify Record clear and blocked-path response and record Vessel wall and window materials. A barrier switch is not a Doppler flowmeter. Confirm the exact model and record the result before changing settings.
Verification: Record clear and blocked-path response and record Vessel wall and window materials
Limites d’application : A barrier switch is not a Doppler flowmeter
42Is rough face-to-face alignment sufficient?
No. Axis, angle, separation and reflections all affect signal. Verify Save signal strength and threshold before adjustment and record Dust, deposits and path obstruction. Dust tolerance does not mean unlimited deposit tolerance. Confirm the exact model and record the result before changing settings.
Verification: Save signal strength and threshold before adjustment and record Dust, deposits and path obstruction
Limites d’application : Dust tolerance does not mean unlimited deposit tolerance
43Can any plastic sheet serve as a window?
No. Transmission and mechanical/process requirements must all be met. Verify Check transmitter/receiver pairing and alignment and record State logic and response. Metal walls are not transparent windows. Confirm the exact model and record the result before changing settings.
Verification: Check transmitter/receiver pairing and alignment and record State logic and response
Limites d’application : Metal walls are not transparent windows
44Is maximum sensitivity the most reliable setting?
No. Maintain adequate clear/blocked contrast and noise margin. Verify Check window material and thickness and record Separation and alignment. Presence detection is not continuous level. Confirm the exact model and record the result before changing settings.
Verification: Check window material and thickness and record Separation and alignment
Limites d’application : Presence detection is not continuous level
45What should be checked for an empty-silo alarm?
Check deposits, alignment and unintended obstruction before changing sensitivity. Verify Record clear and blocked-path response and record Material dielectric and attenuation. A barrier switch is not a Doppler flowmeter. Confirm the exact model and record the result before changing settings.
Verification: Record clear and blocked-path response and record Material dielectric and attenuation
Limites d’application : A barrier switch is not a Doppler flowmeter
46Why can a full silo fail to alarm?
The path may be unblocked, attenuation insufficient or output logic reversed. Verify Save signal strength and threshold before adjustment and record Vessel wall and window materials. Dust tolerance does not mean unlimited deposit tolerance. Confirm the exact model and record the result before changing settings.
Verification: Save signal strength and threshold before adjustment and record Vessel wall and window materials
Limites d’application : Dust tolerance does not mean unlimited deposit tolerance
47Does presence prove material flow?
No. A stationary blockage can produce the same state; flow detection needs a suitable function. Verify Check transmitter/receiver pairing and alignment and record Dust, deposits and path obstruction. Metal walls are not transparent windows. Confirm the exact model and record the result before changing settings.
Verification: Check transmitter/receiver pairing and alignment and record Dust, deposits and path obstruction
Limites d’application : Metal walls are not transparent windows
48Does dust tolerance eliminate cleaning?
No. Dense window deposits differ from airborne dust and can permanently attenuate the path. Verify Check window material and thickness and record State logic and response. Presence detection is not continuous level. Confirm the exact model and record the result before changing settings.
Verification: Check window material and thickness and record State logic and response
Limites d’application : Presence detection is not continuous level
49Should power loss mean alarm or normal?
Define failure states explicitly; lost signal must not automatically mean no material. Verify Record clear and blocked-path response and record Separation and alignment. A barrier switch is not a Doppler flowmeter. Confirm the exact model and record the result before changing settings.
Verification: Record clear and blocked-path response and record Separation and alignment
Limites d’application : A barrier switch is not a Doppler flowmeter
50Why compare clear/blocked margin for replacement?
Equal mounting does not prove equal attenuation capability; test the actual material. Verify Save signal strength and threshold before adjustment and record Material dielectric and attenuation. Dust tolerance does not mean unlimited deposit tolerance. Confirm the exact model and record the result before changing settings.
Verification: Save signal strength and threshold before adjustment and record Material dielectric and attenuation
Limites d’application : Dust tolerance does not mean unlimited deposit tolerance






