Des conditions du procédé au bon instrument
Comprenez les principes de mesure, vérifiez les conditions du procédé, configurez les produits et conservez vos ressources techniques.

La version française n’est pas encore disponible. La version complète en anglais est présentée ci-dessous.

← Retour à la base de connaissances
Guide technique30 min de lectureLangue du contenu: anglaisMis à jour 16 octobre 2026

Electromagnetic flowmeters: 50 selection, application and maintenance questions

50 shared questions for Electromagnetic flowmeters, covering selection, delivery, maintenance, common questions and evidence-based brand comparisons, with verification actions, limits and sources.

Commencer une fiche d’application

Principes communs · Vérifiez chaque modèle

Shared guidance for this product family. Confirm the complete model and application; family-level guidance is not evidence of a particular product specification or approval.

Les principes généraux s’appliquent en complément de la validation du modèle. Les performances, homologations et alternatives dépendent du code de commande complet et des conditions réelles.

1

What does the Electromagnetic flowmeters principle establish, and what does it not establish?

Conductive liquid generates a velocity-related voltage in a magnetic field; bore area converts velocity to volume flow. The principle explains signal generation; it does not establish the range, accuracy, materials or approvals of every model. Review the physical principle and the application limits separately.

Verification: Confirm "Actual conductivity across temperature" and assess "Minimum conductivity is design and size dependent" against the actual application. Record the complete model and document revision used.

Limites d’application : Minimum conductivity is design and size dependent

2

Is the required result measured directly or calculated from other inputs?

Define the quantity to be accepted before selecting a display unit. Conductive liquid generates a velocity-related voltage in a magnetic field; bore area converts velocity to volume flow. For "Actual conductivity across temperature", document output definitions and conversion or compensation conditions; displaying a value does not make it a direct measurement under all conditions.

Verification: Document the process objective, units and reference conditions. Check "Claiming magnetic meters measure oil or gas by principle" and list separate inputs and acceptance methods for calculated results.

Limites d’application : Claiming magnetic meters measure oil or gas by principle

3

Which application information is needed before requesting a quotation?

Prepare at least these five input groups: Actual conductivity across temperature; Flow range and actual bore; Corrosion, solids, abrasion and coating; Pressure, temperature, vacuum and cleaning; Pipe material, lining and potential equalisation. Mark unknown items for confirmation instead of substituting a normal point or an assumed default for all conditions.

Verification: Have process, instrumentation and purchasing roles agree the inputs, particularly "Flow range and actual bore". Resolve missing evidence before requesting application confirmation.

Limites d’application : Minimum conductivity is design and size dependent

4

How should the range be chosen rather than copied from a nominal equipment rating?

Select the range from actual operating conditions and permissible error, then check extremes and installation constraints. For this family: Minimum conductivity is design and size dependent Nominal size or maximum equipment rating need not equal the useful measuring interval.

Verification: List minimum, normal, maximum and abnormal conditions. Check "Corrosion, solids, abrasion and coating" against the documented performance envelope.

Limites d’application : Minimum conductivity is design and size dependent

5

Can a larger turndown claim or display rescaling fix poor low-end performance?

No. Low-end usability depends on the principle, available signal and error mechanisms. A standard full-bore meter is not a partially-filled meter More display digits, software scaling or a stated turndown cannot remove the original noise or installation error.

Verification: Obtain error definitions and limits at the actual low operating point. Use "Low indication → fullness, bore or factor issue → verify configuration" to investigate bias instead of comparing only percent-of-full-scale values.

Limites d’application : A standard full-bore meter is not a partially-filled meter

6

How should compatibility with the measured object and materials be established?

Use the complete measured object and actual exposure, rather than a material name alone. Pressure, temperature, vacuum and cleaning Avoid this family-specific misuse: Confusing protective earth with process reference For non-wetted equipment, assess loads, target materials, signals and environmental compatibility instead.

Verification: List the actual contact or loading parts, seals, insulation and cleaning conditions. Have the responsible parties assess "Materials and pressure/vacuum ratings still constrain service".

Limites d’application : Materials and pressure/vacuum ratings still constrain service

7

Why must abnormal and environmental conditions be listed separately from normal operation?

Normal measurement, temporary excursions and survival limits are different requirements. Materials and pressure/vacuum ratings still constrain service Start-up, cleaning, impacts, power interruption or abnormal environments can determine the necessary construction and protection.

Verification: Complete the worst-case conditions using "Pipe material, lining and potential equalisation" and check "Coating, gas and poor potential equalisation can degrade signals". Separate continuous operating limits from temporary limits in the specification.

Limites d’application : Coating, gas and poor potential equalisation can degrade signals

8

Can the published instrument accuracy be used as the installed system accuracy?

Not without assessment. Specify fluid, conductivity and uncertainty for calibration; empty-pipe and electronic tests are not wet-flow calibration. The installed system also includes object, mounting, signal conversion, environmental and reference effects. Derived results additionally depend on the relevant input uncertainties.

Verification: Agree actual test points, installation conditions and the acceptance reference. Check "Choose a location that stays full without trapped air" and document the system error or uncertainty basis.

Limites d’application : A standard full-bore meter is not a partially-filled meter

9

How should response time, filtering and a stable display be balanced?

A stable indication and fast change detection involve a trade-off; filtering cannot repair incorrect installation or real process variation. Zero drift → potentials, coating or noise → check equalisation and trends Review the complete chain when fast response matters, not merely the display refresh rate.

Verification: Define the shortest relevant event and acceptable delay. Check "Follow liner and sealing-face torque instructions" and verify local output, display and receiving-system response using a controlled change.

Limites d’application : Replacing transmitters without factor checks

10

Which typical applications fit, and which require a specific engineering review?

Typical contexts include: Deionised water: assess actual conductivity; Slurry: balance abrasion, velocity and coating; Plastic pipe: establish a process-reference path. Similar application labels do not establish equivalent conditions. In particular, assess "Coating, gas and poor potential equalisation can degrade signals" before relying on another installation as proof.

Verification: Select the nearest application and compare "Actual conductivity across temperature" and "Pipe material, lining and potential equalisation". Obtain written confirmation where published application limits are exceeded.

Limites d’application : Coating, gas and poor potential equalisation can degrade signals

11

How should a complete order code be defined without unspecified standard options?

Translate required functions, performance and physical interfaces into verifiable options. Minimum conductivity and flow requirements; Liner, electrodes, grounding and compatibility. Options affecting suitability or supply scope should be explicit; terms such as standard or same as existing are insufficient.

Verification: Check the complete order code and selection sheet, especially "Corrosion, solids, abrasion and coating". List accessories, documents, calibration and delivery boundaries separately.

Limites d’application : Claiming magnetic meters measure oil or gas by principle

12

Which mounting and mechanical layout checks belong before ordering?

Choose a location that stays full without trapped air The installation drawing must match the available space and process or mechanical structure. Access for fitting and servicing should be established before delivery.

Verification: Review a dimensioned, oriented site drawing. Use "Pressure, temperature, vacuum and cleaning" and "Materials and pressure/vacuum ratings still constrain service" to confirm connections, support, removal access and safe isolation.

Limites d’application : Materials and pressure/vacuum ratings still constrain service

13

How can supporting infrastructure prevent an instrument that fits but cannot be used?

Match potential equalisation to pipe and electrode design Supporting conditions are part of the measurement system. Matching mechanical connections or signal names alone do not establish power, I/O, grounding or configuration compatibility.

Verification: Confirm "Flanges, length and bore" and "Remote cable and excitation compatibility" against actual terminals, loops and receiving-system settings.

Limites d’application : Confusing protective earth with process reference

14

What is a sensible commissioning sequence before changing correction factors?

Check identity, installation and basic conditions first, then status, output and process response. Follow liner and sealing-face torque instructions Preserve original evidence for unexplained anomalies instead of concealing them with zero or factor adjustments.

Verification: Record factory settings and initial status. Investigate "Empty-pipe alarm → low wetting or electrode issue → inspect process and diagnostics" step by step and change parameters only after identifying the cause and using an authorised procedure.

Limites d’application : Replacing transmitters without factor checks

15

Do identical output units or interface names establish connection compatibility?

No. Establish the represented object and reference conditions: Minimum conductivity and flow requirements. Electrical equipment also needs loop type, scaling, failure behaviour and protocol details checked. Mechanical indicators require clear boundaries between indication and remote-transmission accessories.

Verification: Check the receiving-system variable against "Actual conductivity across temperature" and verify limits, units and abnormal states with the actual equipment. Record wiring, configuration and end-to-end checks against "Match potential equalisation to pipe and electrode design".

Limites d’application : Confusing protective earth with process reference

16

What should a calibration report contain to be relevant to the application?

Specify fluid, conductivity and uncertainty for calibration; empty-pipe and electronic tests are not wet-flow calibration. The report should identify the delivered instrument, measured quantity, conditions, method and results. A general conformity certificate does not establish performance for every option or operating condition.

Verification: Check serial number, points, units, reference equipment and traceability. Compare "Flow range and actual bore" with the calibrated conditions and agree separate acceptance where they differ.

Limites d’application : A standard full-bore meter is not a partially-filled meter

17

How can delivery and site acceptance use reproducible pass criteria?

Route and ground signal cables as specified Agree criteria before testing, including range, conditions, error definition and treatment of anomalies. Similar-looking readings or an unsuitable portable reference are not sufficient acceptance evidence.

Verification: Choose an appropriate reference using "Specify fluid, conductivity and uncertainty for calibration; empty-pipe and electronic tests are not wet-flow calibration.". Record "Actual conductivity across temperature" and test conditions; investigate "Low indication → fullness, bore or factor issue → verify configuration" before deciding on rework or recalibration.

Limites d’application : A standard full-bore meter is not a partially-filled meter

18

What belongs in the quotation and agreement for a non-standard application?

Define why the standard supply is insufficient, the required verification and the responsible parties. Coating, gas and poor potential equalisation can degrade signals; Trusting flow in a partly-filled standard meter. Additional materials, construction, documents or tests depend on actual requirements.

Verification: Attach "Pipe material, lining and potential equalisation" and the deviations. Obtain technical confirmation, additional charges, delivery conditions and acceptance methods; unknown requirements must not be assumed satisfied.

Limites d’application : Coating, gas and poor potential equalisation can degrade signals

19

Where should investigation start when there is no valid reading or output?

Empty-pipe alarm → low wetting or electrode issue → inspect process and diagnostics Distinguish the actual measured condition from device-state and readout or transmission faults. Do not immediately interpret missing data as sensor failure or a zero process value.

Verification: Under appropriate safe isolation, check "Match potential equalisation to pipe and electrode design". Compare local and receiving-end status and record when the fault appeared.

Limites d’application : Claiming magnetic meters measure oil or gas by principle

20

How can unstable readings be separated from genuine process variation?

Zero drift → potentials, coating or noise → check equalisation and trends Compare independent process evidence and raw signals before deciding whether installation, interference or equipment is responsible. More filtering can hide a real abnormal event.

Verification: Keep conditions comparable and record correlation with process or equipment events. Check "Choose a location that stays full without trapped air" and change one factor at a time.

Limites d’application : Replacing transmitters without factor checks

21

How should a persistent high or low bias be investigated before changing factors?

Low indication → fullness, bore or factor issue → verify configuration Systematic bias can arise from units, reference conditions, configuration, installation or the reference method. An unexplained correction can move one operating-point error to other conditions.

Verification: Align quantities, time bases and units first. Review the reference using "Specify fluid, conductivity and uncertainty for calibration; empty-pipe and electronic tests are not wet-flow calibration." and confirm that "Flow range and actual bore" matches the configuration.

Limites d’application : A standard full-bore meter is not a partially-filled meter

22

When is it appropriate to adjust a drifting zero or reference position?

Local/remote mismatch → scaling issue → compare output and PLC Establish a genuine, stable reference condition that meets the method requirements before considering adjustment. Some instruments have no freely adjustable site zero.

Verification: Check "Follow liner and sealing-face torque instructions" and "Specify fluid, conductivity and uncertainty for calibration; empty-pipe and electronic tests are not wet-flow calibration." and retain before-and-after results. If the conditions cannot be established, remove external effects or use a qualified service.

Limites d’application : Replacing transmitters without factor checks

23

Which evidence helps diagnose intermittent alarms or failures?

Dosing-related instability → mixing or conductivity change → correlate diagnostics Intermittent faults need correlated event records, not just a normal display after recovery. Review alarm settings, communication status and actual process abnormalities separately.

Verification: Retain time, status codes, raw trends and the contemporaneous "Pipe material, lining and potential equalisation". Compare "Match potential equalisation to pipe and electrode design" and "Follow liner and sealing-face torque instructions" to locate the failing link.

Limites d’application : Trusting flow in a partly-filled standard meter

24

Why should repeated failures trigger a cause review instead of another identical replacement?

Repeated failures warrant a common-cause assessment. Trusting flow in a partly-filled standard meter If the external conditions remain unchanged, an identical construction or installation can experience the same failure again.

Verification: Summarise failed parts, service time and "Pipe material, lining and potential equalisation". Check "Choose a location that stays full without trapped air" and "Materials and pressure/vacuum ratings still constrain service" and establish corrective action before selecting repair or redesign.

Limites d’application : Materials and pressure/vacuum ratings still constrain service

25

What distinguishes a site comparison, an adjustment and a calibration?

Specify fluid, conductivity and uncertainty for calibration; empty-pipe and electronic tests are not wet-flow calibration. A comparison identifies differences; adjustment changes indication or parameters; calibration establishes a reference relationship under stated conditions. They are not interchangeable claims.

Verification: Define what performance and evidence must be established, using conditions relevant to "Flow range and actual bore". Retain original and adjusted results, references and responsibility records.

Limites d’application : A standard full-bore meter is not a partially-filled meter

26

What must be checked again after replacing an instrument with the same basic model?

The same basic model does not establish identical options, software, calibration or accessories. Remote cable and excitation compatibility; Outputs, totalisation and approvals. Previous system operation does not remove the need to verify a replacement.

Verification: Compare full order codes and revisions. Recheck critical points, failure states and interfaces using "Route and ground signal cables as specified" before handover.

Limites d’application : Trusting flow in a partly-filled standard meter

27

Can every published maximum rating be achieved simultaneously?

No. Minimum conductivity is design and size dependent Maximum values usually relate to particular options and conditions. Temperature, load, pressure, materials, speed or signal conditions may constrain one another.

Verification: Review "Corrosion, solids, abrasion and coating" and "Pipe material, lining and potential equalisation" together. Obtain confirmation for the combined conditions instead of assembling unrelated maxima from separate pages.

Limites d’application : Minimum conductivity is design and size dependent

28

Does a missing signal or zero indication establish that the process value is zero?

No. Empty-pipe alarm → low wetting or electrode issue → inspect process and diagnostics Indication, measurement and transmission have distinct possible failure modes. Also consider "Claiming magnetic meters measure oil or gas by principle"; establish the actual process condition independently.

Verification: Check available status or failure indications and "Flanges, length and bore". For interlocks, follow the complete safety design rather than substituting a zero value for diagnosis.

Limites d’application : Claiming magnetic meters measure oil or gas by principle

29

Does one acceptable test point establish compliance across the working range?

No. Specify fluid, conductivity and uncertainty for calibration; empty-pipe and electronic tests are not wet-flow calibration. Test points and directions must reflect the working interval, relevant error mechanisms and acceptance purpose. Multiple points, reversal or load tests depend on the method.

Verification: Define acceptance coverage against "Flow range and actual bore" and include critical operating points. Mark conditions outside the tests as unverified.

Limites d’application : A standard full-bore meter is not a partially-filled meter

30

Are the largest range, highest accuracy class and most options always preferable?

Not necessarily. Options should serve the required objective; excess configuration can add cost, complexity or incompatibility. A standard full-bore meter is not a partially-filled meter; Confusing protective earth with process reference. Establish essential requirements before comparing optional benefits.

Verification: Document the objective in "Actual conductivity across temperature" and why "Minimum conductivity and flow requirements" is needed. Compare performance at actual working points rather than one headline metric.

Limites d’application : A standard full-bore meter is not a partially-filled meter

31

Can every maintenance or recalibration interval simply be fixed at one year?

Not independently of risk and history. Specify fluid, conductivity and uncertainty for calibration; empty-pipe and electronic tests are not wet-flow calibration. Intervals depend on applicable law or contract, conditions, drift, maintenance and failure evidence. Generic advice cannot replace mandatory requirements.

Verification: Use "Local/remote mismatch → scaling issue → compare output and PLC" and "Trusting flow in a partly-filled standard meter" to establish and review an initial plan. Retain the justification and approval for interval changes.

Limites d’application : Trusting flow in a partly-filled standard meter

32

Can parts from different brands be mixed if their physical interfaces fit?

Physical fit is insufficient. Liner, electrodes, grounding and compatibility; Flanges, length and bore. Matching, materials, signals, calibration and approval boundaries can change with the combination.

Verification: Check the complete combination against "Match potential equalisation to pipe and electrode design" and obtain compatibility and acceptance evidence. An unconfirmed assembly must not be described as an approved system.

Limites d’application : Confusing protective earth with process reference

33

Does a hazardous-area, hygienic or safety label establish suitability for that duty?

Check the exact order configuration and valid documents rather than a series name. Outputs, totalisation and approvals "Coating, gas and poor potential equalisation can degrade signals" also matters; certificates, installation conditions and restrictions together define suitability.

Verification: Obtain certificate identifiers, covered models and special conditions and match them to the site. Similar names do not grant functional-safety or legal-metrology approval.

Limites d’application : Coating, gas and poor potential equalisation can degrade signals

34

What evidence makes the final result acceptable, reproducible and sustainable?

Establish the chain from quantity definition and application limits through configuration, mounting, reference and operating status. Route and ground signal cables as specified A normal indication or brochure alone cannot demonstrate continuing system reliability.

Verification: Put "Actual conductivity across temperature", "Specify fluid, conductivity and uncertainty for calibration; empty-pipe and electronic tests are not wet-flow calibration." and "Dosing-related instability → mixing or conductivity change → correlate diagnostics" into the technical, acceptance and maintenance records, with responsibility for reviewing excursions.

Limites d’application : Coating, gas and poor potential equalisation can degrade signals

35

Can a DOWESTON model replace an installed instrument from another brand?

Possibly, after a full configuration and application comparison. A basic model name or matching output is not proof of equivalent replacement. Minimum conductivity and flow requirements; Liner, electrodes, grounding and compatibility; Flanges, length and bore. Record conclusions on material differences.

Verification: Provide the original full order code, data sheet and site conditions. Check "Remote cable and excitation compatibility" and "Outputs, totalisation and approvals" and obtain the necessary test and approval evidence before replacement.

Limites d’application : Coating, gas and poor potential equalisation can degrade signals

36

Why choose DOWESTON, and what would make that reasoning evidence-based?

Base the decision on project compliance and documented delivery or service, rather than a slogan. "Actual conductivity across temperature" and "Minimum conductivity is design and size dependent" are important family-specific checks. Claim only benefits supported by the offered product documents and written commitments.

Verification: Request the proposed configuration matching "Minimum conductivity and flow requirements", test evidence and delivery/service terms. Do not infer unverified performance, approvals, origin or service life.

Limites d’application : Minimum conductivity is design and size dependent

37

How can competing brands be compared beyond a single accuracy or price figure?

Use identical conditions and supply boundaries. Minimum conductivity and flow requirements; Flanges, length and bore; Outputs, totalisation and approvals. Quotes with different ranges, compensation, accessories or calibration scope can conceal material differences.

Verification: Compare "Flow range and actual bore", "A standard full-bore meter is not a partially-filled meter" and mounting/acceptance conditions. Separate demonstrated, unverified and inapplicable items; do not claim unproven overall superiority.

Limites d’application : A standard full-bore meter is not a partially-filled meter

38

How should purchasing compare cost without overlooking additions or rework?

Compare complete supply and use-cycle costs, not only the main instrument price. Choose a location that stays full without trapped air; Specify fluid, conductivity and uncertainty for calibration; empty-pipe and electronic tests are not wet-flow calibration. List the actual installation, supporting equipment, calibration, consumables, downtime and service requirements without assuming any brand is always cheaper.

Verification: Use the same "Minimum conductivity and flow requirements" configuration and "Pipe material, lining and potential equalisation" boundary. Separate equipment, accessories, commissioning and maintenance responsibilities and retain a traceable comparison.

Limites d’application : Coating, gas and poor potential equalisation can degrade signals

39

Can a magmeter measure deionised water?

Compare actual minimum conductivity and low-flow signal conditions with the exact sensor specifications.

Verification: Provide minimum conductivity, temperature and flow for the exact sensor.

Limites d’application : Minimum conductivity is design and size dependent

40

Why are most oils and gases unsuitable for magmeters?

Standard magmeters require sufficiently conductive liquid; identify the actual phase and conductivity before selecting technology.

Verification: Confirm fluid composition, conductivity and phase.

Limites d’application : A standard full-bore meter is not a partially-filled meter

41

Is 316L always adequate for a magmeter?

No. Assess all wetted materials against chemistry, temperature, cleaning, abrasion and vacuum conditions.

Verification: List operating and cleaning media, concentration, temperature, abrasion and vacuum.

Limites d’application : Materials and pressure/vacuum ratings still constrain service

42

Is enclosure earth enough on plastic pipe?

Not necessarily. Follow the sensor-specific process potential-equalisation arrangement in addition to protective earthing.

Verification: Draw protective earth and process-reference paths with each pipe material.

Limites d’application : Coating, gas and poor potential equalisation can degrade signals

43

Does empty-pipe detection allow half-full operation?

No. Detection is not level-dependent area correction; use an explicitly suitable partially-filled design if needed.

Verification: Check minimum fill level, pipe slope and any partially-filled-meter qualification.

Limites d’application : Minimum conductivity is design and size dependent

44

Why do gasket and tightening details matter?

Incorrect sealing or force can damage the liner or disturb flow; use the exact model's installation procedure.

Verification: Record gasket bore, lining type, tightening procedure and natural pipe alignment.

Limites d’application : A standard full-bore meter is not a partially-filled meter

45

Why can dosing cause unstable magmeter readings?

Correlate dosing, mixing, conductivity, gas and diagnostics before using damping or changing process design.

Verification: Correlate dosing events, flow, conductivity and alarms.

Limites d’application : Materials and pressure/vacuum ratings still constrain service

46

Should I reset zero when a magmeter drifts at shutdown?

First exclude leakage, empty pipe, potential differences, coating and noise; adjust zero only under valid conditions.

Verification: Save no-flow and fullness evidence, electrode diagnostics and grounding arrangement.

Limites d’application : Coating, gas and poor potential equalisation can degrade signals

47

How do I isolate a local/PLC discrepancy?

Compare units, output span, direction, fault handling and pulse factors before changing sensor calibration.

Verification: Document 4/20 mA values, units, span and totaliser pulse factor.

Limites d’application : Minimum conductivity is design and size dependent

48

Does slurry density directly scale magnetic volume flow?

No simple density-ratio correction applies; inspect accompanying gas, coating, conductivity and flow changes.

Verification: Separate volume measurement from density-based mass conversion.

Limites d’application : A standard full-bore meter is not a partially-filled meter

49

Does electrode verification prove total flow accuracy?

No. Verify installation and actual-flow performance separately from the electrical checks. A successful electronic test cannot establish pipe fullness, actual bore or the field flow profile.

Verification: List the distinct scope of self-tests, installation checks and calibration.

Limites d’application : Materials and pressure/vacuum ratings still constrain service

50

Can DOWESTON replace another brand's magmeter component?

Do not assume cross-brand sensor/transmitter compatibility; evaluate the complete documented combination.

Verification: Define whether replacement covers a complete meter or a proven compatible component.

Limites d’application : Coating, gas and poor potential equalisation can degrade signals

Appliquez ces connaissances à la sélection

Clients et achats

Vérifiez les conditions réelles et les critères de réception dans l’article et la documentation du produit. Soumettez les points ouverts au service technique DOWESTON.

Équipes commerciales et techniques

Notez les questions du client et ses conditions de service. Vérifiez la plage, les raccordements et les conditions d’utilisation dans la documentation du modèle sélectionné.

Transformez les questions en critères de sélection

Relevez le fluide, les raccordements, le montage et les critères de réception du produit, puis examinez les points ouverts avec DOWESTON.

Commencer une fiche d’application
Pas encore connecté à DOWESTON ?
Créez un compte pour commencer la sélection, consulter les prix et recevoir notre lettre d'information sur les dernières nouveautés.
Produits et services
Doweston propose une gamme de services pour vous aider à construire rapidement vos systèmes d'instrumentation automatisés. Contactez-nous pour en savoir plus.
Prêt à acheter ?
Si vous souhaitez acheter des produits,
contactez simplement notre équipe commerciale — nous serons ravis de vous aider.
Qui sommes-nous
DOWESTON fournit des solutions de mesure précises et fiables
— des produits de détection et de capteurs fiables dans tous les domaines !
Une demande de service ?
Si vous souhaitez optimiser votre production et réduire les arrêts,
nous pouvons vous aider à choisir les pièces de rechange et les services adaptés.
Modifier la configuration

Nom du produit

Marque

Modèle

Confirmer les modifications Annuler
Votre écran est peut-être trop petit pour une navigation optimale.
Nous vous recommandons de continuer sur un ordinateur,
ou contactez immédiatement un ingénieur pour votre sélection !
Service plus rapide ? Appelez le
400-888-4436
Continuer la navigation