La version française n’est pas encore disponible. La version complète en anglais est présentée ci-dessous.
← Retour à la base de connaissancesWireless vibration monitoring: 50 selection, application and maintenance questions
50 shared questions for Wireless vibration monitoring, covering selection, delivery, maintenance, common questions and evidence-based brand comparisons, with verification actions, limits and sources.
Conservez vos ressources techniques
Conservez un brouillon dans ce navigateur, puis importez-le manuellement dans votre bibliothèque après connexion.
La création de compte suit le processus habituel d’inscription et d’approbation. L’enregistrement de ressources n’ouvre pas automatiquement l’accès aux prix ni aux autres autorisations commerciales.
Shared guidance for this product family. Confirm the complete model and application; family-level guidance is not evidence of a particular product specification or approval.
Les principes généraux s’appliquent en complément de la validation du modèle. Les performances, homologations et alternatives dépendent du code de commande complet et des conditions réelles.
1What does the Wireless vibration monitoring principle establish, and what does it not establish?
Wireless vibration monitoring acquires or computes vibration information locally and sends waveforms or features by radio. Acquisition intervals, processing windows and upload periods are distinct parameters. The principle explains signal generation; it does not establish the range, accuracy, materials or approvals of every model. Review the physical principle and the application limits separately.
Verification: Confirm "Target faults, vibration quantity and frequency band" and assess "Periodic trending can miss short events between acquisitions" against the actual application. Record the complete model and document revision used.
Limites d’application : Periodic trending can miss short events between acquisitions
2Is the required result measured directly or calculated from other inputs?
Define the quantity to be accepted before selecting a display unit. Wireless vibration monitoring acquires or computes vibration information locally and sends waveforms or features by radio. Acquisition intervals, processing windows and upload periods are distinct parameters. For "Target faults, vibration quantity and frequency band", document output definitions and conversion or compensation conditions; displaying a value does not make it a direct measurement under all conditions.
Verification: Document the process objective, units and reference conditions. Check "Treating one upload per minute as continuous waveform acquisition" and list separate inputs and acceptance methods for calculated results.
Limites d’application : Treating one upload per minute as continuous waveform acquisition
3Which application information is needed before requesting a quotation?
Prepare at least these five input groups: Target faults, vibration quantity and frequency band; Acquisition window, measurement interval and event duration; Waveform/feature transfer, retention and alarm requirements; Mounting, radio distance, obstructions and gateway layout; Battery, temperature, network permissions and radio approvals. Mark unknown items for confirmation instead of substituting a normal point or an assumed default for all conditions.
Verification: Have process, instrumentation and purchasing roles agree the inputs, particularly "Acquisition window, measurement interval and event duration". Resolve missing evidence before requesting application confirmation.
Limites d’application : Periodic trending can miss short events between acquisitions
4How should the range be chosen rather than copied from a nominal equipment rating?
Select the range from actual operating conditions and permissible error, then check extremes and installation constraints. For this family: Periodic trending can miss short events between acquisitions Nominal size or maximum equipment rating need not equal the useful measuring interval.
Verification: List minimum, normal, maximum and abnormal conditions. Check "Waveform/feature transfer, retention and alarm requirements" against the documented performance envelope.
Limites d’application : Periodic trending can miss short events between acquisitions
5Can a larger turndown claim or display rescaling fix poor low-end performance?
No. Low-end usability depends on the principle, available signal and error mechanisms. Upload frequency is not waveform sample rate or bandwidth More display digits, software scaling or a stated turndown cannot remove the original noise or installation error.
Verification: Obtain error definitions and limits at the actual low operating point. Use "Amplitude mismatch: inspect band, window and feature definition" to investigate bias instead of comparing only percent-of-full-scale values.
Limites d’application : Upload frequency is not waveform sample rate or bandwidth
6How should compatibility with the measured object and materials be established?
Use the complete measured object and actual exposure, rather than a material name alone. Mounting, radio distance, obstructions and gateway layout Avoid this family-specific misuse: Plotting missing wireless data as zero vibration without a quality flag For non-wetted equipment, assess loads, target materials, signals and environmental compatibility instead.
Verification: List the actual contact or loading parts, seals, insulation and cleaning conditions. Have the responsible parties assess "Battery life depends on temperature, acquisition and communication duty".
Limites d’application : Battery life depends on temperature, acquisition and communication duty
7Why must abnormal and environmental conditions be listed separately from normal operation?
Normal measurement, temporary excursions and survival limits are different requirements. Battery life depends on temperature, acquisition and communication duty Start-up, cleaning, impacts, power interruption or abnormal environments can determine the necessary construction and protection.
Verification: Complete the worst-case conditions using "Battery, temperature, network permissions and radio approvals" and check "Wireless condition monitoring is not automatically suitable for low-latency tripping". Separate continuous operating limits from temporary limits in the specification.
Limites d’application : Wireless condition monitoring is not automatically suitable for low-latency tripping
8Can the published instrument accuracy be used as the installed system accuracy?
Not without assessment. Alongside vibration calibration, verify scheduling, timing, radio transfer and missing-data behaviour; received data do not prove all events were completely measured. The installed system also includes object, mounting, signal conversion, environmental and reference effects. Derived results additionally depend on the relevant input uncertainties.
Verification: Agree actual test points, installation conditions and the acceptance reference. Check "Choose a mechanically valid measurement point before assessing radio coverage" and document the system error or uncertainty basis.
Limites d’application : Upload frequency is not waveform sample rate or bandwidth
9How should response time, filtering and a stable display be balanced?
A stable indication and fast change detection involve a trade-off; filtering cannot repair incorrect installation or real process variation. Trend step: inspect mounting, operating state and algorithm version Review the complete chain when fast response matters, not merely the display refresh rate.
Verification: Define the shortest relevant event and acceptable delay. Check "Check local measurement, transfer and server times and missing-data flags" and verify local output, display and receiving-system response using a controlled change.
Limites d’application : Promising coverage in a metal plant from line-of-sight range alone
10Which typical applications fit, and which require a specific engineering review?
Typical contexts include: Periodic condition trends on distributed equipment; Noncritical monitoring where cabling is difficult; Predictive-maintenance evidence with controlled data paths. Similar application labels do not establish equivalent conditions. In particular, assess "Wireless condition monitoring is not automatically suitable for low-latency tripping" before relying on another installation as proof.
Verification: Select the nearest application and compare "Target faults, vibration quantity and frequency band" and "Battery, temperature, network permissions and radio approvals". Obtain written confirmation where published application limits are exceeded.
Limites d’application : Wireless condition monitoring is not automatically suitable for low-latency tripping
11How should a complete order code be defined without unspecified standard options?
Translate required functions, performance and physical interfaces into verifiable options. Quantity, band, axes and acquisition strategy; Mounting, temperature and environmental protection. Options affecting suitability or supply scope should be explicit; terms such as standard or same as existing are insufficient.
Verification: Check the complete order code and selection sheet, especially "Waveform/feature transfer, retention and alarm requirements". List accessories, documents, calibration and delivery boundaries separately.
Limites d’application : Treating one upload per minute as continuous waveform acquisition
12Which mounting and mechanical layout checks belong before ordering?
Choose a mechanically valid measurement point before assessing radio coverage The installation drawing must match the available space and process or mechanical structure. Access for fitting and servicing should be established before delivery.
Verification: Review a dimensioned, oriented site drawing. Use "Mounting, radio distance, obstructions and gateway layout" and "Battery life depends on temperature, acquisition and communication duty" to confirm connections, support, removal access and safe isolation.
Limites d’application : Battery life depends on temperature, acquisition and communication duty
13How can supporting infrastructure prevent an instrument that fits but cannot be used?
Test gateway coverage with actual obstructions and running equipment Supporting conditions are part of the measurement system. Matching mechanical connections or signal names alone do not establish power, I/O, grounding or configuration compatibility.
Verification: Confirm "Radio protocol, regional approval, gateway and data interface" and "Battery, time sync, offline storage and retry behaviour" against actual terminals, loops and receiving-system settings.
Limites d’application : Plotting missing wireless data as zero vibration without a quality flag
14What is a sensible commissioning sequence before changing correction factors?
Check identity, installation and basic conditions first, then status, output and process response. Check local measurement, transfer and server times and missing-data flags Preserve original evidence for unexplained anomalies instead of concealing them with zero or factor adjustments.
Verification: Record factory settings and initial status. Investigate "No update: check last measurement time, transfer state, battery and gateway" step by step and change parameters only after identifying the cause and using an authorised procedure.
Limites d’application : Promising coverage in a metal plant from line-of-sight range alone
15Do identical output units or interface names establish connection compatibility?
No. Establish the represented object and reference conditions: Quantity, band, axes and acquisition strategy. Electrical equipment also needs loop type, scaling, failure behaviour and protocol details checked. Mechanical indicators require clear boundaries between indication and remote-transmission accessories.
Verification: Check the receiving-system variable against "Target faults, vibration quantity and frequency band" and verify limits, units and abnormal states with the actual equipment. Record wiring, configuration and end-to-end checks against "Test gateway coverage with actual obstructions and running equipment".
Limites d’application : Plotting missing wireless data as zero vibration without a quality flag
16What should a calibration report contain to be relevant to the application?
Alongside vibration calibration, verify scheduling, timing, radio transfer and missing-data behaviour; received data do not prove all events were completely measured. The report should identify the delivered instrument, measured quantity, conditions, method and results. A general conformity certificate does not establish performance for every option or operating condition.
Verification: Check serial number, points, units, reference equipment and traceability. Compare "Acquisition window, measurement interval and event duration" with the calibrated conditions and agree separate acceptance where they differ.
Limites d’application : Upload frequency is not waveform sample rate or bandwidth
17How can delivery and site acceptance use reproducible pass criteria?
Test outages, low battery, recovery and permission changes end to end Agree criteria before testing, including range, conditions, error definition and treatment of anomalies. Similar-looking readings or an unsuitable portable reference are not sufficient acceptance evidence.
Verification: Choose an appropriate reference using "Alongside vibration calibration, verify scheduling, timing, radio transfer and missing-data behaviour; received data do not prove all events were completely measured.". Record "Target faults, vibration quantity and frequency band" and test conditions; investigate "Amplitude mismatch: inspect band, window and feature definition" before deciding on rework or recalibration.
Limites d’application : Upload frequency is not waveform sample rate or bandwidth
18What belongs in the quotation and agreement for a non-standard application?
Define why the standard supply is insufficient, the required verification and the responsible parties. Wireless condition monitoring is not automatically suitable for low-latency tripping; Ignoring battery, firmware and algorithm changes in trend comparability. Additional materials, construction, documents or tests depend on actual requirements.
Verification: Attach "Battery, temperature, network permissions and radio approvals" and the deviations. Obtain technical confirmation, additional charges, delivery conditions and acceptance methods; unknown requirements must not be assumed satisfied.
Limites d’application : Wireless condition monitoring is not automatically suitable for low-latency tripping
19Where should investigation start when there is no valid reading or output?
No update: check last measurement time, transfer state, battery and gateway Distinguish the actual measured condition from device-state and readout or transmission faults. Do not immediately interpret missing data as sensor failure or a zero process value.
Verification: Under appropriate safe isolation, check "Test gateway coverage with actual obstructions and running equipment". Compare local and receiving-end status and record when the fault appeared.
Limites d’application : Treating one upload per minute as continuous waveform acquisition
20How can unstable readings be separated from genuine process variation?
Trend step: inspect mounting, operating state and algorithm version Compare independent process evidence and raw signals before deciding whether installation, interference or equipment is responsible. More filtering can hide a real abnormal event.
Verification: Keep conditions comparable and record correlation with process or equipment events. Check "Choose a mechanically valid measurement point before assessing radio coverage" and change one factor at a time.
Limites d’application : Promising coverage in a metal plant from line-of-sight range alone
21How should a persistent high or low bias be investigated before changing factors?
Amplitude mismatch: inspect band, window and feature definition Systematic bias can arise from units, reference conditions, configuration, installation or the reference method. An unexplained correction can move one operating-point error to other conditions.
Verification: Align quantities, time bases and units first. Review the reference using "Alongside vibration calibration, verify scheduling, timing, radio transfer and missing-data behaviour; received data do not prove all events were completely measured." and confirm that "Acquisition window, measurement interval and event duration" matches the configuration.
Limites d’application : Upload frequency is not waveform sample rate or bandwidth
22When is it appropriate to adjust a drifting zero or reference position?
Time drift: inspect local clock, synchronisation and receipt timestamp Establish a genuine, stable reference condition that meets the method requirements before considering adjustment. Some instruments have no freely adjustable site zero.
Verification: Check "Check local measurement, transfer and server times and missing-data flags" and "Alongside vibration calibration, verify scheduling, timing, radio transfer and missing-data behaviour; received data do not prove all events were completely measured." and retain before-and-after results. If the conditions cannot be established, remove external effects or use a qualified service.
Limites d’application : Promising coverage in a metal plant from line-of-sight range alone
23Which evidence helps diagnose intermittent alarms or failures?
Intermittent loss: inspect metal obstructions, interference, retries and capacity Intermittent faults need correlated event records, not just a normal display after recovery. Review alarm settings, communication status and actual process abnormalities separately.
Verification: Retain time, status codes, raw trends and the contemporaneous "Battery, temperature, network permissions and radio approvals". Compare "Test gateway coverage with actual obstructions and running equipment" and "Check local measurement, transfer and server times and missing-data flags" to locate the failing link.
Limites d’application : Ignoring battery, firmware and algorithm changes in trend comparability
24Why should repeated failures trigger a cause review instead of another identical replacement?
Repeated failures warrant a common-cause assessment. Ignoring battery, firmware and algorithm changes in trend comparability If the external conditions remain unchanged, an identical construction or installation can experience the same failure again.
Verification: Summarise failed parts, service time and "Battery, temperature, network permissions and radio approvals". Check "Choose a mechanically valid measurement point before assessing radio coverage" and "Battery life depends on temperature, acquisition and communication duty" and establish corrective action before selecting repair or redesign.
Limites d’application : Battery life depends on temperature, acquisition and communication duty
25What distinguishes a site comparison, an adjustment and a calibration?
Alongside vibration calibration, verify scheduling, timing, radio transfer and missing-data behaviour; received data do not prove all events were completely measured. A comparison identifies differences; adjustment changes indication or parameters; calibration establishes a reference relationship under stated conditions. They are not interchangeable claims.
Verification: Define what performance and evidence must be established, using conditions relevant to "Acquisition window, measurement interval and event duration". Retain original and adjusted results, references and responsibility records.
Limites d’application : Upload frequency is not waveform sample rate or bandwidth
26What must be checked again after replacing an instrument with the same basic model?
The same basic model does not establish identical options, software, calibration or accessories. Battery, time sync, offline storage and retry behaviour; Approval, cybersecurity and protection-duty scope documents. Previous system operation does not remove the need to verify a replacement.
Verification: Compare full order codes and revisions. Recheck critical points, failure states and interfaces using "Test outages, low battery, recovery and permission changes end to end" before handover.
Limites d’application : Ignoring battery, firmware and algorithm changes in trend comparability
27Can every published maximum rating be achieved simultaneously?
No. Periodic trending can miss short events between acquisitions Maximum values usually relate to particular options and conditions. Temperature, load, pressure, materials, speed or signal conditions may constrain one another.
Verification: Review "Waveform/feature transfer, retention and alarm requirements" and "Battery, temperature, network permissions and radio approvals" together. Obtain confirmation for the combined conditions instead of assembling unrelated maxima from separate pages.
Limites d’application : Periodic trending can miss short events between acquisitions
28Does a missing signal or zero indication establish that the process value is zero?
No. No update: check last measurement time, transfer state, battery and gateway Indication, measurement and transmission have distinct possible failure modes. Also consider "Treating one upload per minute as continuous waveform acquisition"; establish the actual process condition independently.
Verification: Check available status or failure indications and "Radio protocol, regional approval, gateway and data interface". For interlocks, follow the complete safety design rather than substituting a zero value for diagnosis.
Limites d’application : Treating one upload per minute as continuous waveform acquisition
29Does one acceptable test point establish compliance across the working range?
No. Alongside vibration calibration, verify scheduling, timing, radio transfer and missing-data behaviour; received data do not prove all events were completely measured. Test points and directions must reflect the working interval, relevant error mechanisms and acceptance purpose. Multiple points, reversal or load tests depend on the method.
Verification: Define acceptance coverage against "Acquisition window, measurement interval and event duration" and include critical operating points. Mark conditions outside the tests as unverified.
Limites d’application : Upload frequency is not waveform sample rate or bandwidth
30Are the largest range, highest accuracy class and most options always preferable?
Not necessarily. Options should serve the required objective; excess configuration can add cost, complexity or incompatibility. Upload frequency is not waveform sample rate or bandwidth; Plotting missing wireless data as zero vibration without a quality flag. Establish essential requirements before comparing optional benefits.
Verification: Document the objective in "Target faults, vibration quantity and frequency band" and why "Quantity, band, axes and acquisition strategy" is needed. Compare performance at actual working points rather than one headline metric.
Limites d’application : Upload frequency is not waveform sample rate or bandwidth
31Can every maintenance or recalibration interval simply be fixed at one year?
Not independently of risk and history. Alongside vibration calibration, verify scheduling, timing, radio transfer and missing-data behaviour; received data do not prove all events were completely measured. Intervals depend on applicable law or contract, conditions, drift, maintenance and failure evidence. Generic advice cannot replace mandatory requirements.
Verification: Use "Time drift: inspect local clock, synchronisation and receipt timestamp" and "Ignoring battery, firmware and algorithm changes in trend comparability" to establish and review an initial plan. Retain the justification and approval for interval changes.
Limites d’application : Ignoring battery, firmware and algorithm changes in trend comparability
32Can parts from different brands be mixed if their physical interfaces fit?
Physical fit is insufficient. Mounting, temperature and environmental protection; Radio protocol, regional approval, gateway and data interface. Matching, materials, signals, calibration and approval boundaries can change with the combination.
Verification: Check the complete combination against "Test gateway coverage with actual obstructions and running equipment" and obtain compatibility and acceptance evidence. An unconfirmed assembly must not be described as an approved system.
Limites d’application : Plotting missing wireless data as zero vibration without a quality flag
33Does a hazardous-area, hygienic or safety label establish suitability for that duty?
Check the exact order configuration and valid documents rather than a series name. Approval, cybersecurity and protection-duty scope documents "Wireless condition monitoring is not automatically suitable for low-latency tripping" also matters; certificates, installation conditions and restrictions together define suitability.
Verification: Obtain certificate identifiers, covered models and special conditions and match them to the site. Similar names do not grant functional-safety or legal-metrology approval.
Limites d’application : Wireless condition monitoring is not automatically suitable for low-latency tripping
34What evidence makes the final result acceptable, reproducible and sustainable?
Establish the chain from quantity definition and application limits through configuration, mounting, reference and operating status. Test outages, low battery, recovery and permission changes end to end A normal indication or brochure alone cannot demonstrate continuing system reliability.
Verification: Put "Target faults, vibration quantity and frequency band", "Alongside vibration calibration, verify scheduling, timing, radio transfer and missing-data behaviour; received data do not prove all events were completely measured." and "Intermittent loss: inspect metal obstructions, interference, retries and capacity" into the technical, acceptance and maintenance records, with responsibility for reviewing excursions.
Limites d’application : Wireless condition monitoring is not automatically suitable for low-latency tripping
35Can a DOWESTON model replace an installed instrument from another brand?
Possibly, after a full configuration and application comparison. A basic model name or matching output is not proof of equivalent replacement. Quantity, band, axes and acquisition strategy; Mounting, temperature and environmental protection; Radio protocol, regional approval, gateway and data interface. Record conclusions on material differences.
Verification: Provide the original full order code, data sheet and site conditions. Check "Battery, time sync, offline storage and retry behaviour" and "Approval, cybersecurity and protection-duty scope documents" and obtain the necessary test and approval evidence before replacement.
Limites d’application : Wireless condition monitoring is not automatically suitable for low-latency tripping
36Why choose DOWESTON, and what would make that reasoning evidence-based?
Base the decision on project compliance and documented delivery or service, rather than a slogan. "Target faults, vibration quantity and frequency band" and "Periodic trending can miss short events between acquisitions" are important family-specific checks. Claim only benefits supported by the offered product documents and written commitments.
Verification: Request the proposed configuration matching "Quantity, band, axes and acquisition strategy", test evidence and delivery/service terms. Do not infer unverified performance, approvals, origin or service life.
Limites d’application : Periodic trending can miss short events between acquisitions
37How can competing brands be compared beyond a single accuracy or price figure?
Use identical conditions and supply boundaries. Quantity, band, axes and acquisition strategy; Radio protocol, regional approval, gateway and data interface; Approval, cybersecurity and protection-duty scope documents. Quotes with different ranges, compensation, accessories or calibration scope can conceal material differences.
Verification: Compare "Acquisition window, measurement interval and event duration", "Upload frequency is not waveform sample rate or bandwidth" and mounting/acceptance conditions. Separate demonstrated, unverified and inapplicable items; do not claim unproven overall superiority.
Limites d’application : Upload frequency is not waveform sample rate or bandwidth
38How should purchasing compare cost without overlooking additions or rework?
Compare complete supply and use-cycle costs, not only the main instrument price. Choose a mechanically valid measurement point before assessing radio coverage; Alongside vibration calibration, verify scheduling, timing, radio transfer and missing-data behaviour; received data do not prove all events were completely measured. List the actual installation, supporting equipment, calibration, consumables, downtime and service requirements without assuming any brand is always cheaper.
Verification: Use the same "Quantity, band, axes and acquisition strategy" configuration and "Battery, temperature, network permissions and radio approvals" boundary. Separate equipment, accessories, commissioning and maintenance responsibilities and retain a traceable comparison.
Limites d’application : Wireless condition monitoring is not automatically suitable for low-latency tripping
39Does one upload per minute establish continuous measurement for the minute?
No. A device may acquire one short window and upload features, or process continuously locally. Define the complete scheduling strategy and event coverage.
Verification: Obtain all timing parameters and test known short events, including events between acquisition windows.
Limites d’application : Periodic trending can miss short events between acquisitions
40Can an RMS value from a wireless sensor reconstruct the original waveform?
Normally not. RMS summarises a window and different waveforms can share it. Without raw data or adequate features, missing spectral information cannot be reconstructed reliably.
Verification: Check exported data types, retained windows and algorithms before choosing for the analysis task.
Limites d’application : Upload frequency is not waveform sample rate or bandwidth
41Does successful gateway reception establish measurement accuracy?
No. Network availability is separate from measurement validity; incorrect axis or poor mounting can still transmit plausible values reliably.
Verification: Verify mounting and a vibration reference first, then radio coverage, retaining separate acceptance records.
Limites d’application : Battery life depends on temperature, acquisition and communication duty
42Why is plotting zero during a connection loss misleading?
Zero can falsely suggest a quiet or stopped machine. Preserve quality flags, measurement time and last-valid status instead of manufacturing a continuous trend.
Verification: Simulate loss and confirm displays, exports and alarms mark missing data without presenting stale values as new.
Limites d’application : Wireless condition monitoring is not automatically suitable for low-latency tripping
43Why is an advertised battery life not a site replacement interval?
Published life assumes particular temperature, sensing and radio duty. Retries, waveform transfers and temperature can alter consumption; use the actual task.
Verification: Obtain test conditions, trend actual duty and charge and define warning/replacement responsibility.
Limites d’application : Periodic trending can miss short events between acquisitions
44Does a strong RSSI guarantee no data loss around metal structures?
No. Interference, changing obstructions, gateway capacity and protocol behaviour affect delivery. Signal strength alone is only partial evidence.
Verification: Measure loss, retries and maximum delay under operating conditions rather than retaining one RSSI snapshot.
Limites d’application : Upload frequency is not waveform sample rate or bandwidth
45Can wireless points support phase or orbit analysis?
Such analysis needs suitable synchronisation, timing and raw waveforms. Independently scheduled feature uploads do not establish phase relationships.
Verification: Specify phase error and band, check synchronisation evidence and test a common event across points.
Limites d’application : Battery life depends on temperature, acquisition and communication duty
46Can server receipt time replace the actual measurement time?
No. Buffering, retries and queues add varying delay. Receipt time is not necessarily acquisition time; event correlation needs defined timestamp semantics.
Verification: Check device timestamp, timezone/sync and receipt fields and compare delay using a known event.
Limites d’application : Wireless condition monitoring is not automatically suitable for low-latency tripping
47Does a trend step after firmware update necessarily mean deterioration?
No. Algorithms, filtering, calibration or feature definitions can change values. Retain revision changes as events and assess data comparability.
Verification: Retain configurations and reference measurements, review release notes and compare at the same conditions.
Limites d’application : Periodic trending can miss short events between acquisitions
48Can a wireless vibration alarm directly provide emergency-stop protection?
Monitoring does not establish protection. Communication delay, data loss, power and failure response must be assessed; ordinary trends are not automatically low-latency safety functions.
Verification: Have machine and safety owners define the function and validate the complete documented chain.
Limites d’application : Upload frequency is not waveform sample rate or bandwidth
49Can the old trend baseline be reused after replacing a wireless sensor?
Confirm location, axis, mounting, sensitivity, acquisition and algorithm equivalence and link the new identity correctly; mismatched records can create artificial changes.
Verification: Record replacement and compare under equivalent conditions, documenting whether the baseline continues or is rebuilt.
Limites d’application : Battery life depends on temperature, acquisition and communication duty
50Why do radio approval and cybersecurity belong in selection?
Regional radio rules and site access policy can constrain deployment; accounts, keys and remote updates affect governance. A successful connection is not operating approval.
Verification: Check regional evidence and site approval and define access, update and decommissioning responsibilities.
Limites d’application : Wireless condition monitoring is not automatically suitable for low-latency tripping






