La edición en español aún no está disponible. A continuación se muestra la versión completa en inglés.
← Volver a la base de conocimientosFloat level instruments and switches: 50 selection, application and maintenance questions
50 shared questions for Float level instruments and switches, covering selection, delivery, maintenance, common questions and evidence-based brand comparisons, with verification actions, limits and sources.
Guarde sus referencias técnicas
Guarde un borrador en este navegador e impórtelo manualmente en Mi biblioteca después de iniciar sesión.
La cuenta sigue el proceso habitual de registro y aprobación. Guardar recursos no habilita automáticamente el acceso a precios u otros permisos comerciales.
Shared guidance for this product family. Confirm the complete model and application; family-level guidance is not evidence of a particular product specification or approval.
Use los principios generales junto con la validación del modelo. El rendimiento, las homologaciones y las alternativas dependen del código de pedido completo y las condiciones reales.
1What does the Float level instruments and switches principle establish, and what does it not establish?
Buoyancy moves a float with the liquid, and a sensing arrangement provides level or switch output. The principle explains signal generation; it does not establish the range, accuracy, materials or approvals of every model. Review the physical principle and the application limits separately.
Verification: Confirm "Minimum density and temperature variation" and assess "Minimum float density requirements must be met" against the actual application. Record the complete model and document revision used.
Límites de aplicación: Minimum float density requirements must be met
2Is the required result measured directly or calculated from other inputs?
Define the quantity to be accepted before selecting a display unit. Buoyancy moves a float with the liquid, and a sensing arrangement provides level or switch output. For "Minimum density and temperature variation", document output definitions and conversion or compensation conditions; displaying a value does not make it a direct measurement under all conditions.
Verification: Document the process objective, units and reference conditions. Check "Minimum float density requirements must be met" and list separate inputs and acceptance methods for calculated results.
Límites de aplicación: Minimum float density requirements must be met
3Which application information is needed before requesting a quotation?
Prepare at least these five input groups: Minimum density and temperature variation; Float material and pressure rating; Viscosity, solids and buildup; Trip, reset and orientation; Output type and load. Mark unknown items for confirmation instead of substituting a normal point or an assumed default for all conditions.
Verification: Have process, instrumentation and purchasing roles agree the inputs, particularly "Float material and pressure rating". Resolve missing evidence before requesting application confirmation.
Límites de aplicación: Minimum float density requirements must be met
4How should the range be chosen rather than copied from a nominal equipment rating?
Select the range from actual operating conditions and permissible error, then check extremes and installation constraints. For this family: Minimum float density requirements must be met Nominal size or maximum equipment rating need not equal the useful measuring interval.
Verification: List minimum, normal, maximum and abnormal conditions. Check "Viscosity, solids and buildup" against the documented performance envelope.
Límites de aplicación: Minimum float density requirements must be met
5Can a larger turndown claim or display rescaling fix poor low-end performance?
No. Low-end usability depends on the principle, available signal and error mechanisms. Float pressure rating is distinct from housing rating More display digits, software scaling or a stated turndown cannot remove the original noise or installation error.
Verification: Obtain error definitions and limits at the actual low operating point. Use "How should wave-induced chatter be addressed → Assess location, guidance and controlled deadband without masking genuine limits. → Ensure free float travel and record Trip, reset and orientation" to investigate bias instead of comparing only percent-of-full-scale values.
Límites de aplicación: Float pressure rating is distinct from housing rating
6How should compatibility with the measured object and materials be established?
Use the complete measured object and actual exposure, rather than a material name alone. Trip, reset and orientation Avoid this family-specific misuse: Float pressure rating is distinct from housing rating For non-wetted equipment, assess loads, target materials, signals and environmental compatibility instead.
Verification: List the actual contact or loading parts, seals, insulation and cleaning conditions. Have the responsible parties assess "A level switch is not a continuous level transmitter".
Límites de aplicación: A level switch is not a continuous level transmitter
7Why must abnormal and environmental conditions be listed separately from normal operation?
Normal measurement, temporary excursions and survival limits are different requirements. A level switch is not a continuous level transmitter Start-up, cleaning, impacts, power interruption or abnormal environments can determine the necessary construction and protection.
Verification: Complete the worst-case conditions using "Output type and load" and check "Deadband and contact rating are construction-specific". Separate continuous operating limits from temporary limits in the specification.
Límites de aplicación: Deadband and contact rating are construction-specific
8Can the published instrument accuracy be used as the installed system accuracy?
Not without assessment. Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. The installed system also includes object, mounting, signal conversion, environmental and reference effects. Derived results additionally depend on the relevant input uncertainties.
Verification: Agree actual test points, installation conditions and the acceptance reference. Check "Ensure free float travel" and document the system error or uncertainty basis.
Límites de aplicación: Float pressure rating is distinct from housing rating
9How should response time, filtering and a stable display be balanced?
A stable indication and fast change detection involve a trade-off; filtering cannot repair incorrect installation or real process variation. Does a sunken float always mean insufficient density → Leakage, collapse or mechanical sticking can also cause it. → Provide appropriate inductive-load protection and record Viscosity, solids and buildup Review the complete chain when fast response matters, not merely the display refresh rate.
Verification: Define the shortest relevant event and acceptable delay. Check "Verify trip and reset with the actual liquid" and verify local output, display and receiving-system response using a controlled change.
Límites de aplicación: A level switch is not a continuous level transmitter
10Which typical applications fit, and which require a specific engineering review?
Typical contexts include: Tank high/low limits; Water-tank pump control; Liquid presence/absence monitoring. Similar application labels do not establish equivalent conditions. In particular, assess "Deadband and contact rating are construction-specific" before relying on another installation as proof.
Verification: Select the nearest application and compare "Minimum density and temperature variation" and "Output type and load". Obtain written confirmation where published application limits are exceeded.
Límites de aplicación: Deadband and contact rating are construction-specific
11How should a complete order code be defined without unspecified standard options?
Translate required functions, performance and physical interfaces into verifiable options. Minimum density and temperature variation; Float material and pressure rating. Options affecting suitability or supply scope should be explicit; terms such as standard or same as existing are insufficient.
Verification: Check the complete order code and selection sheet, especially "Viscosity, solids and buildup". List accessories, documents, calibration and delivery boundaries separately.
Límites de aplicación: Minimum float density requirements must be met
12Which mounting and mechanical layout checks belong before ordering?
Ensure free float travel The installation drawing must match the available space and process or mechanical structure. Access for fitting and servicing should be established before delivery.
Verification: Review a dimensioned, oriented site drawing. Use "Trip, reset and orientation" and "A level switch is not a continuous level transmitter" to confirm connections, support, removal access and safe isolation.
Límites de aplicación: A level switch is not a continuous level transmitter
13How can supporting infrastructure prevent an instrument that fits but cannot be used?
Avoid direct filling and agitation impact Supporting conditions are part of the measurement system. Matching mechanical connections or signal names alone do not establish power, I/O, grounding or configuration compatibility.
Verification: Confirm "Ensure free float travel" and "Verify output, failure state and receiving-system compatibility" against actual terminals, loops and receiving-system settings.
Límites de aplicación: Float pressure rating is distinct from housing rating
14What is a sensible commissioning sequence before changing correction factors?
Check identity, installation and basic conditions first, then status, output and process response. Verify trip and reset with the actual liquid Preserve original evidence for unexplained anomalies instead of concealing them with zero or factor adjustments.
Verification: Record factory settings and initial status. Investigate "Why can a float pass continuity but fail under load → Load damage, wiring or leakage can differ from an offline low-current test. → Verify trip and reset with the actual liquid and record Float material and pressure rating" step by step and change parameters only after identifying the cause and using an authorised procedure.
Límites de aplicación: A level switch is not a continuous level transmitter
15Do identical output units or interface names establish connection compatibility?
No. Establish the represented object and reference conditions: Minimum density and temperature variation. Electrical equipment also needs loop type, scaling, failure behaviour and protocol details checked. Mechanical indicators require clear boundaries between indication and remote-transmission accessories.
Verification: Check the receiving-system variable against "Minimum density and temperature variation" and verify limits, units and abnormal states with the actual equipment. Record wiring, configuration and end-to-end checks against "Avoid direct filling and agitation impact".
Límites de aplicación: Float pressure rating is distinct from housing rating
16What should a calibration report contain to be relevant to the application?
Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. The report should identify the delivered instrument, measured quantity, conditions, method and results. A general conformity certificate does not establish performance for every option or operating condition.
Verification: Check serial number, points, units, reference equipment and traceability. Compare "Float material and pressure rating" with the calibrated conditions and agree separate acceptance where they differ.
Límites de aplicación: Float pressure rating is distinct from housing rating
17How can delivery and site acceptance use reproducible pass criteria?
Provide appropriate inductive-load protection Agree criteria before testing, including range, conditions, error definition and treatment of anomalies. Similar-looking readings or an unsuitable portable reference are not sufficient acceptance evidence.
Verification: Choose an appropriate reference using "Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment.". Record "Minimum density and temperature variation" and test conditions; investigate "How should wave-induced chatter be addressed → Assess location, guidance and controlled deadband without masking genuine limits. → Ensure free float travel and record Trip, reset and orientation" before deciding on rework or recalibration.
Límites de aplicación: Float pressure rating is distinct from housing rating
18What belongs in the quotation and agreement for a non-standard application?
Define why the standard supply is insufficient, the required verification and the responsible parties. Deadband and contact rating are construction-specific; Deadband and contact rating are construction-specific. Additional materials, construction, documents or tests depend on actual requirements.
Verification: Attach "Output type and load" and the deviations. Obtain technical confirmation, additional charges, delivery conditions and acceptance methods; unknown requirements must not be assumed satisfied.
Límites de aplicación: Deadband and contact rating are construction-specific
19Where should investigation start when there is no valid reading or output?
Why can a float pass continuity but fail under load → Load damage, wiring or leakage can differ from an offline low-current test. → Verify trip and reset with the actual liquid and record Float material and pressure rating Distinguish the actual measured condition from device-state and readout or transmission faults. Do not immediately interpret missing data as sensor failure or a zero process value.
Verification: Under appropriate safe isolation, check "Avoid direct filling and agitation impact". Compare local and receiving-end status and record when the fault appeared.
Límites de aplicación: Minimum float density requirements must be met
20How can unstable readings be separated from genuine process variation?
Does a sunken float always mean insufficient density → Leakage, collapse or mechanical sticking can also cause it. → Provide appropriate inductive-load protection and record Viscosity, solids and buildup Compare independent process evidence and raw signals before deciding whether installation, interference or equipment is responsible. More filtering can hide a real abnormal event.
Verification: Keep conditions comparable and record correlation with process or equipment events. Check "Ensure free float travel" and change one factor at a time.
Límites de aplicación: A level switch is not a continuous level transmitter
21How should a persistent high or low bias be investigated before changing factors?
How should wave-induced chatter be addressed → Assess location, guidance and controlled deadband without masking genuine limits. → Ensure free float travel and record Trip, reset and orientation Systematic bias can arise from units, reference conditions, configuration, installation or the reference method. An unexplained correction can move one operating-point error to other conditions.
Verification: Align quantities, time bases and units first. Review the reference using "Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment." and confirm that "Float material and pressure rating" matches the configuration.
Límites de aplicación: Float pressure rating is distinct from housing rating
22When is it appropriate to adjust a drifting zero or reference position?
Does a dry test prove process suitability → No. It does not verify buoyancy, immersion or adhesion in the actual liquid. → Avoid direct filling and agitation impact and record Output type and load Establish a genuine, stable reference condition that meets the method requirements before considering adjustment. Some instruments have no freely adjustable site zero.
Verification: Check "Verify trip and reset with the actual liquid" and "Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment." and retain before-and-after results. If the conditions cannot be established, remove external effects or use a qualified service.
Límites de aplicación: A level switch is not a continuous level transmitter
23Which evidence helps diagnose intermittent alarms or failures?
Should multiple floats be checked for contradictory states → Yes. Impossible combinations can indicate wiring, sticking or logic faults. → Verify trip and reset with the actual liquid and record Minimum density and temperature variation Intermittent faults need correlated event records, not just a normal display after recovery. Review alarm settings, communication status and actual process abnormalities separately.
Verification: Retain time, status codes, raw trends and the contemporaneous "Output type and load". Compare "Avoid direct filling and agitation impact" and "Verify trip and reset with the actual liquid" to locate the failing link.
Límites de aplicación: Deadband and contact rating are construction-specific
24Why should repeated failures trigger a cause review instead of another identical replacement?
Repeated failures warrant a common-cause assessment. Deadband and contact rating are construction-specific If the external conditions remain unchanged, an identical construction or installation can experience the same failure again.
Verification: Summarise failed parts, service time and "Output type and load". Check "Ensure free float travel" and "A level switch is not a continuous level transmitter" and establish corrective action before selecting repair or redesign.
Límites de aplicación: A level switch is not a continuous level transmitter
25What distinguishes a site comparison, an adjustment and a calibration?
Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. A comparison identifies differences; adjustment changes indication or parameters; calibration establishes a reference relationship under stated conditions. They are not interchangeable claims.
Verification: Define what performance and evidence must be established, using conditions relevant to "Float material and pressure rating". Retain original and adjusted results, references and responsibility records.
Límites de aplicación: Float pressure rating is distinct from housing rating
26What must be checked again after replacing an instrument with the same basic model?
The same basic model does not establish identical options, software, calibration or accessories. Verify output, failure state and receiving-system compatibility; Confirm certificates, calibration and site change approval in writing. Previous system operation does not remove the need to verify a replacement.
Verification: Compare full order codes and revisions. Recheck critical points, failure states and interfaces using "Provide appropriate inductive-load protection" before handover.
Límites de aplicación: Deadband and contact rating are construction-specific
27Can every published maximum rating be achieved simultaneously?
No. Minimum float density requirements must be met Maximum values usually relate to particular options and conditions. Temperature, load, pressure, materials, speed or signal conditions may constrain one another.
Verification: Review "Viscosity, solids and buildup" and "Output type and load" together. Obtain confirmation for the combined conditions instead of assembling unrelated maxima from separate pages.
Límites de aplicación: Minimum float density requirements must be met
28Does a missing signal or zero indication establish that the process value is zero?
No. Why can a float pass continuity but fail under load → Load damage, wiring or leakage can differ from an offline low-current test. → Verify trip and reset with the actual liquid and record Float material and pressure rating Indication, measurement and transmission have distinct possible failure modes. Also consider "Minimum float density requirements must be met"; establish the actual process condition independently.
Verification: Check available status or failure indications and "Ensure free float travel". For interlocks, follow the complete safety design rather than substituting a zero value for diagnosis.
Límites de aplicación: Minimum float density requirements must be met
29Does one acceptable test point establish compliance across the working range?
No. Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. Test points and directions must reflect the working interval, relevant error mechanisms and acceptance purpose. Multiple points, reversal or load tests depend on the method.
Verification: Define acceptance coverage against "Float material and pressure rating" and include critical operating points. Mark conditions outside the tests as unverified.
Límites de aplicación: Float pressure rating is distinct from housing rating
30Are the largest range, highest accuracy class and most options always preferable?
Not necessarily. Options should serve the required objective; excess configuration can add cost, complexity or incompatibility. Float pressure rating is distinct from housing rating; Float pressure rating is distinct from housing rating. Establish essential requirements before comparing optional benefits.
Verification: Document the objective in "Minimum density and temperature variation" and why "Minimum density and temperature variation" is needed. Compare performance at actual working points rather than one headline metric.
Límites de aplicación: Float pressure rating is distinct from housing rating
31Can every maintenance or recalibration interval simply be fixed at one year?
Not independently of risk and history. Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. Intervals depend on applicable law or contract, conditions, drift, maintenance and failure evidence. Generic advice cannot replace mandatory requirements.
Verification: Use "Does a dry test prove process suitability → No. It does not verify buoyancy, immersion or adhesion in the actual liquid. → Avoid direct filling and agitation impact and record Output type and load" and "Deadband and contact rating are construction-specific" to establish and review an initial plan. Retain the justification and approval for interval changes.
Límites de aplicación: Deadband and contact rating are construction-specific
32Can parts from different brands be mixed if their physical interfaces fit?
Physical fit is insufficient. Float material and pressure rating; Ensure free float travel. Matching, materials, signals, calibration and approval boundaries can change with the combination.
Verification: Check the complete combination against "Avoid direct filling and agitation impact" and obtain compatibility and acceptance evidence. An unconfirmed assembly must not be described as an approved system.
Límites de aplicación: Float pressure rating is distinct from housing rating
33Does a hazardous-area, hygienic or safety label establish suitability for that duty?
Check the exact order configuration and valid documents rather than a series name. Confirm certificates, calibration and site change approval in writing "Deadband and contact rating are construction-specific" also matters; certificates, installation conditions and restrictions together define suitability.
Verification: Obtain certificate identifiers, covered models and special conditions and match them to the site. Similar names do not grant functional-safety or legal-metrology approval.
Límites de aplicación: Deadband and contact rating are construction-specific
34What evidence makes the final result acceptable, reproducible and sustainable?
Establish the chain from quantity definition and application limits through configuration, mounting, reference and operating status. Provide appropriate inductive-load protection A normal indication or brochure alone cannot demonstrate continuing system reliability.
Verification: Put "Minimum density and temperature variation", "Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment." and "Should multiple floats be checked for contradictory states → Yes. Impossible combinations can indicate wiring, sticking or logic faults. → Verify trip and reset with the actual liquid and record Minimum density and temperature variation" into the technical, acceptance and maintenance records, with responsibility for reviewing excursions.
Límites de aplicación: Deadband and contact rating are construction-specific
35Can a DOWESTON model replace an installed instrument from another brand?
Possibly, after a full configuration and application comparison. A basic model name or matching output is not proof of equivalent replacement. Minimum density and temperature variation; Float material and pressure rating; Ensure free float travel. Record conclusions on material differences.
Verification: Provide the original full order code, data sheet and site conditions. Check "Verify output, failure state and receiving-system compatibility" and "Confirm certificates, calibration and site change approval in writing" and obtain the necessary test and approval evidence before replacement.
Límites de aplicación: Deadband and contact rating are construction-specific
36Why choose DOWESTON, and what would make that reasoning evidence-based?
Base the decision on project compliance and documented delivery or service, rather than a slogan. "Minimum density and temperature variation" and "Minimum float density requirements must be met" are important family-specific checks. Claim only benefits supported by the offered product documents and written commitments.
Verification: Request the proposed configuration matching "Minimum density and temperature variation", test evidence and delivery/service terms. Do not infer unverified performance, approvals, origin or service life.
Límites de aplicación: Minimum float density requirements must be met
37How can competing brands be compared beyond a single accuracy or price figure?
Use identical conditions and supply boundaries. Minimum density and temperature variation; Ensure free float travel; Confirm certificates, calibration and site change approval in writing. Quotes with different ranges, compensation, accessories or calibration scope can conceal material differences.
Verification: Compare "Float material and pressure rating", "Float pressure rating is distinct from housing rating" and mounting/acceptance conditions. Separate demonstrated, unverified and inapplicable items; do not claim unproven overall superiority.
Límites de aplicación: Float pressure rating is distinct from housing rating
38How should purchasing compare cost without overlooking additions or rework?
Compare complete supply and use-cycle costs, not only the main instrument price. Ensure free float travel; Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. List the actual installation, supporting equipment, calibration, consumables, downtime and service requirements without assuming any brand is always cheaper.
Verification: Use the same "Minimum density and temperature variation" configuration and "Output type and load" boundary. Separate equipment, accessories, commissioning and maintenance responsibilities and retain a traceable comparison.
Límites de aplicación: Deadband and contact rating are construction-specific
39Can one float serve every liquid?
No. Buoyancy, compatibility, temperature and pressure must all be suitable. Verify Ensure free float travel and record Minimum density and temperature variation. Minimum float density requirements must be met. Confirm the exact model and record the result before changing settings.
Verification: Ensure free float travel and record Minimum density and temperature variation
Límites de aplicación: Minimum float density requirements must be met
40Why is the switching level not necessarily the float center?
Immersion depth and magnetic geometry determine the actual switching level. Verify Avoid direct filling and agitation impact and record Float material and pressure rating. Float pressure rating is distinct from housing rating. Confirm the exact model and record the result before changing settings.
Verification: Avoid direct filling and agitation impact and record Float material and pressure rating
Límites de aplicación: Float pressure rating is distinct from housing rating
41Can an interface float automatically measure total level?
No. It is designed for a specific density relationship between two liquids. Verify Verify trip and reset with the actual liquid and record Viscosity, solids and buildup. A level switch is not a continuous level transmitter. Confirm the exact model and record the result before changing settings.
Verification: Verify trip and reset with the actual liquid and record Viscosity, solids and buildup
Límites de aplicación: A level switch is not a continuous level transmitter
42What happens if mounting orientation is reversed?
Switch direction, travel and mechanical limits may change. Verify Provide appropriate inductive-load protection and record Trip, reset and orientation. Deadband and contact rating are construction-specific. Confirm the exact model and record the result before changing settings.
Verification: Provide appropriate inductive-load protection and record Trip, reset and orientation
Límites de aplicación: Deadband and contact rating are construction-specific
43Why are viscous liquids challenging?
Adhesion and deposits restrict travel and temperature changes alter buoyancy and drag. Verify Ensure free float travel and record Output type and load. Minimum float density requirements must be met. Confirm the exact model and record the result before changing settings.
Verification: Ensure free float travel and record Output type and load
Límites de aplicación: Minimum float density requirements must be met
44Can a reed contact directly drive any solenoid?
No. Inrush and inductive transients may exceed its limits. Verify Avoid direct filling and agitation impact and record Minimum density and temperature variation. Float pressure rating is distinct from housing rating. Confirm the exact model and record the result before changing settings.
Verification: Avoid direct filling and agitation impact and record Minimum density and temperature variation
Límites de aplicación: Float pressure rating is distinct from housing rating
45Why can a float pass continuity but fail under load?
Load damage, wiring or leakage can differ from an offline low-current test. Verify Verify trip and reset with the actual liquid and record Float material and pressure rating. A level switch is not a continuous level transmitter. Confirm the exact model and record the result before changing settings.
Verification: Verify trip and reset with the actual liquid and record Float material and pressure rating
Límites de aplicación: A level switch is not a continuous level transmitter
46Does a sunken float always mean insufficient density?
Leakage, collapse or mechanical sticking can also cause it. Verify Provide appropriate inductive-load protection and record Viscosity, solids and buildup. Deadband and contact rating are construction-specific. Confirm the exact model and record the result before changing settings.
Verification: Provide appropriate inductive-load protection and record Viscosity, solids and buildup
Límites de aplicación: Deadband and contact rating are construction-specific
47How should wave-induced chatter be addressed?
Assess location, guidance and controlled deadband without masking genuine limits. Verify Ensure free float travel and record Trip, reset and orientation. Minimum float density requirements must be met. Confirm the exact model and record the result before changing settings.
Verification: Ensure free float travel and record Trip, reset and orientation
Límites de aplicación: Minimum float density requirements must be met
48Does a dry test prove process suitability?
No. It does not verify buoyancy, immersion or adhesion in the actual liquid. Verify Avoid direct filling and agitation impact and record Output type and load. Float pressure rating is distinct from housing rating. Confirm the exact model and record the result before changing settings.
Verification: Avoid direct filling and agitation impact and record Output type and load
Límites de aplicación: Float pressure rating is distinct from housing rating
49Should multiple floats be checked for contradictory states?
Yes. Impossible combinations can indicate wiring, sticking or logic faults. Verify Verify trip and reset with the actual liquid and record Minimum density and temperature variation. A level switch is not a continuous level transmitter. Confirm the exact model and record the result before changing settings.
Verification: Verify trip and reset with the actual liquid and record Minimum density and temperature variation
Límites de aplicación: A level switch is not a continuous level transmitter
50Is equal stem length sufficient for replacement?
No. Compare density, float pressure, switching points, materials and load. Verify Provide appropriate inductive-load protection and record Float material and pressure rating. Deadband and contact rating are construction-specific. Confirm the exact model and record the result before changing settings.
Verification: Provide appropriate inductive-load protection and record Float material and pressure rating
Límites de aplicación: Deadband and contact rating are construction-specific






