La edición en español aún no está disponible. A continuación se muestra la versión completa en inglés.
← Volver a la base de conocimientosDisplacer level transmitters: 50 selection, application and maintenance questions
50 shared questions for Displacer level transmitters, covering selection, delivery, maintenance, common questions and evidence-based brand comparisons, with verification actions, limits and sources.
Guarde sus referencias técnicas
Guarde un borrador en este navegador e impórtelo manualmente en Mi biblioteca después de iniciar sesión.
La cuenta sigue el proceso habitual de registro y aprobación. Guardar recursos no habilita automáticamente el acceso a precios u otros permisos comerciales.
Shared guidance for this product family. Confirm the complete model and application; family-level guidance is not evidence of a particular product specification or approval.
Use los principios generales junto con la validación del modelo. El rendimiento, las homologaciones y las alternativas dependen del código de pedido completo y las condiciones reales.
1What does the Displacer level transmitters principle establish, and what does it not establish?
A displacer senses buoyancy changes as immersed volume changes, using a spring or torque mechanism. The principle explains signal generation; it does not establish the range, accuracy, materials or approvals of every model. Review the physical principle and the application limits separately.
Verification: Confirm "Upper/lower phase densities and temperature" and assess "A displacer is not a freely floating float" against the actual application. Record the complete model and document revision used.
Límites de aplicación: A displacer is not a freely floating float
2Is the required result measured directly or calculated from other inputs?
Define the quantity to be accepted before selecting a display unit. A displacer senses buoyancy changes as immersed volume changes, using a spring or torque mechanism. For "Upper/lower phase densities and temperature", document output definitions and conversion or compensation conditions; displaying a value does not make it a direct measurement under all conditions.
Verification: Document the process objective, units and reference conditions. Check "A displacer is not a freely floating float" and list separate inputs and acceptance methods for calculated results.
Límites de aplicación: A displacer is not a freely floating float
3Which application information is needed before requesting a quotation?
Prepare at least these five input groups: Upper/lower phase densities and temperature; Displacer volume, weight and length; Torque-tube or spring data; External chamber and orientation; Level or interface objective. Mark unknown items for confirmation instead of substituting a normal point or an assumed default for all conditions.
Verification: Have process, instrumentation and purchasing roles agree the inputs, particularly "Displacer volume, weight and length". Resolve missing evidence before requesting application confirmation.
Límites de aplicación: A displacer is not a freely floating float
4How should the range be chosen rather than copied from a nominal equipment rating?
Select the range from actual operating conditions and permissible error, then check extremes and installation constraints. For this family: A displacer is not a freely floating float Nominal size or maximum equipment rating need not equal the useful measuring interval.
Verification: List minimum, normal, maximum and abnormal conditions. Check "Torque-tube or spring data" against the documented performance envelope.
Límites de aplicación: A displacer is not a freely floating float
5Can a larger turndown claim or display rescaling fix poor low-end performance?
No. Low-end usability depends on the principle, available signal and error mechanisms. Density changes affect calibration More display digits, software scaling or a stated turndown cannot remove the original noise or installation error.
Verification: Obtain error definitions and limits at the actual low operating point. Use "Why can hot-state error differ from room-temperature error → Both process density and mechanical characteristics can change with temperature. → Verify suspension, orientation and mechanical zero and record External chamber and orientation" to investigate bias instead of comparing only percent-of-full-scale values.
Límites de aplicación: Density changes affect calibration
6How should compatibility with the measured object and materials be established?
Use the complete measured object and actual exposure, rather than a material name alone. External chamber and orientation Avoid this family-specific misuse: Density changes affect calibration For non-wetted equipment, assess loads, target materials, signals and environmental compatibility instead.
Verification: List the actual contact or loading parts, seals, insulation and cleaning conditions. Have the responsible parties assess "Vapor density cannot always be ignored at high pressure".
Límites de aplicación: Vapor density cannot always be ignored at high pressure
7Why must abnormal and environmental conditions be listed separately from normal operation?
Normal measurement, temporary excursions and survival limits are different requirements. Vapor density cannot always be ignored at high pressure Start-up, cleaning, impacts, power interruption or abnormal environments can determine the necessary construction and protection.
Verification: Complete the worst-case conditions using "Level or interface objective" and check "Dry weight simulation requires the specified procedure". Separate continuous operating limits from temporary limits in the specification.
Límites de aplicación: Dry weight simulation requires the specified procedure
8Can the published instrument accuracy be used as the installed system accuracy?
Not without assessment. Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. The installed system also includes object, mounting, signal conversion, environmental and reference effects. Derived results additionally depend on the relevant input uncertainties.
Verification: Agree actual test points, installation conditions and the acceptance reference. Check "Verify suspension, orientation and mechanical zero" and document the system error or uncertainty basis.
Límites de aplicación: Density changes affect calibration
9How should response time, filtering and a stable display be balanced?
A stable indication and fast change detection involve a trade-off; filtering cannot repair incorrect installation or real process variation. Can zero trim fix a post-maintenance span error → No. Check suspension weight, geometry and torque data. → Record densities and torque parameters and record Torque-tube or spring data Review the complete chain when fast response matters, not merely the display refresh rate.
Verification: Define the shortest relevant event and acceptable delay. Check "Maintain correct chamber communication" and verify local output, display and receiving-system response using a controlled change.
Límites de aplicación: Vapor density cannot always be ignored at high pressure
10Which typical applications fit, and which require a specific engineering review?
Typical contexts include: Separator interface; Process-vessel level; External-chamber monitoring. Similar application labels do not establish equivalent conditions. In particular, assess "Dry weight simulation requires the specified procedure" before relying on another installation as proof.
Verification: Select the nearest application and compare "Upper/lower phase densities and temperature" and "Level or interface objective". Obtain written confirmation where published application limits are exceeded.
Límites de aplicación: Dry weight simulation requires the specified procedure
11How should a complete order code be defined without unspecified standard options?
Translate required functions, performance and physical interfaces into verifiable options. Upper/lower phase densities and temperature; Displacer volume, weight and length. Options affecting suitability or supply scope should be explicit; terms such as standard or same as existing are insufficient.
Verification: Check the complete order code and selection sheet, especially "Torque-tube or spring data". List accessories, documents, calibration and delivery boundaries separately.
Límites de aplicación: A displacer is not a freely floating float
12Which mounting and mechanical layout checks belong before ordering?
Verify suspension, orientation and mechanical zero The installation drawing must match the available space and process or mechanical structure. Access for fitting and servicing should be established before delivery.
Verification: Review a dimensioned, oriented site drawing. Use "External chamber and orientation" and "Vapor density cannot always be ignored at high pressure" to confirm connections, support, removal access and safe isolation.
Límites de aplicación: Vapor density cannot always be ignored at high pressure
13How can supporting infrastructure prevent an instrument that fits but cannot be used?
Ensure clearance from the chamber wall Supporting conditions are part of the measurement system. Matching mechanical connections or signal names alone do not establish power, I/O, grounding or configuration compatibility.
Verification: Confirm "Verify suspension, orientation and mechanical zero" and "Verify output, failure state and receiving-system compatibility" against actual terminals, loops and receiving-system settings.
Límites de aplicación: Density changes affect calibration
14What is a sensible commissioning sequence before changing correction factors?
Check identity, installation and basic conditions first, then status, output and process response. Maintain correct chamber communication Preserve original evidence for unexplained anomalies instead of concealing them with zero or factor adjustments.
Verification: Record factory settings and initial status. Investigate "Why can level stick while electronics appear healthy → The displacer, suspension or chamber may be mechanically obstructed. → Maintain correct chamber communication and record Displacer volume, weight and length" step by step and change parameters only after identifying the cause and using an authorised procedure.
Límites de aplicación: Vapor density cannot always be ignored at high pressure
15Do identical output units or interface names establish connection compatibility?
No. Establish the represented object and reference conditions: Upper/lower phase densities and temperature. Electrical equipment also needs loop type, scaling, failure behaviour and protocol details checked. Mechanical indicators require clear boundaries between indication and remote-transmission accessories.
Verification: Check the receiving-system variable against "Upper/lower phase densities and temperature" and verify limits, units and abnormal states with the actual equipment. Record wiring, configuration and end-to-end checks against "Ensure clearance from the chamber wall".
Límites de aplicación: Density changes affect calibration
16What should a calibration report contain to be relevant to the application?
Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. The report should identify the delivered instrument, measured quantity, conditions, method and results. A general conformity certificate does not establish performance for every option or operating condition.
Verification: Check serial number, points, units, reference equipment and traceability. Compare "Displacer volume, weight and length" with the calibrated conditions and agree separate acceptance where they differ.
Límites de aplicación: Density changes affect calibration
17How can delivery and site acceptance use reproducible pass criteria?
Record densities and torque parameters Agree criteria before testing, including range, conditions, error definition and treatment of anomalies. Similar-looking readings or an unsuitable portable reference are not sufficient acceptance evidence.
Verification: Choose an appropriate reference using "Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment.". Record "Upper/lower phase densities and temperature" and test conditions; investigate "Why can hot-state error differ from room-temperature error → Both process density and mechanical characteristics can change with temperature. → Verify suspension, orientation and mechanical zero and record External chamber and orientation" before deciding on rework or recalibration.
Límites de aplicación: Density changes affect calibration
18What belongs in the quotation and agreement for a non-standard application?
Define why the standard supply is insufficient, the required verification and the responsible parties. Dry weight simulation requires the specified procedure; Dry weight simulation requires the specified procedure. Additional materials, construction, documents or tests depend on actual requirements.
Verification: Attach "Level or interface objective" and the deviations. Obtain technical confirmation, additional charges, delivery conditions and acceptance methods; unknown requirements must not be assumed satisfied.
Límites de aplicación: Dry weight simulation requires the specified procedure
19Where should investigation start when there is no valid reading or output?
Why can level stick while electronics appear healthy → The displacer, suspension or chamber may be mechanically obstructed. → Maintain correct chamber communication and record Displacer volume, weight and length Distinguish the actual measured condition from device-state and readout or transmission faults. Do not immediately interpret missing data as sensor failure or a zero process value.
Verification: Under appropriate safe isolation, check "Ensure clearance from the chamber wall". Compare local and receiving-end status and record when the fault appeared.
Límites de aplicación: A displacer is not a freely floating float
20How can unstable readings be separated from genuine process variation?
Can zero trim fix a post-maintenance span error → No. Check suspension weight, geometry and torque data. → Record densities and torque parameters and record Torque-tube or spring data Compare independent process evidence and raw signals before deciding whether installation, interference or equipment is responsible. More filtering can hide a real abnormal event.
Verification: Keep conditions comparable and record correlation with process or equipment events. Check "Verify suspension, orientation and mechanical zero" and change one factor at a time.
Límites de aplicación: Vapor density cannot always be ignored at high pressure
21How should a persistent high or low bias be investigated before changing factors?
Why can hot-state error differ from room-temperature error → Both process density and mechanical characteristics can change with temperature. → Verify suspension, orientation and mechanical zero and record External chamber and orientation Systematic bias can arise from units, reference conditions, configuration, installation or the reference method. An unexplained correction can move one operating-point error to other conditions.
Verification: Align quantities, time bases and units first. Review the reference using "Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment." and confirm that "Displacer volume, weight and length" matches the configuration.
Límites de aplicación: Density changes affect calibration
22When is it appropriate to adjust a drifting zero or reference position?
Can arbitrary weights be used for dry calibration → No. Weight simulation depends on the defined buoyancy and mechanism geometry. → Ensure clearance from the chamber wall and record Level or interface objective Establish a genuine, stable reference condition that meets the method requirements before considering adjustment. Some instruments have no freely adjustable site zero.
Verification: Check "Maintain correct chamber communication" and "Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment." and retain before-and-after results. If the conditions cannot be established, remove external effects or use a qualified service.
Límites de aplicación: Vapor density cannot always be ignored at high pressure
23Which evidence helps diagnose intermittent alarms or failures?
Does a displacer directly measure inventory mass → No. Volume geometry and density are additionally required. → Maintain correct chamber communication and record Upper/lower phase densities and temperature Intermittent faults need correlated event records, not just a normal display after recovery. Review alarm settings, communication status and actual process abnormalities separately.
Verification: Retain time, status codes, raw trends and the contemporaneous "Level or interface objective". Compare "Ensure clearance from the chamber wall" and "Maintain correct chamber communication" to locate the failing link.
Límites de aplicación: Dry weight simulation requires the specified procedure
24Why should repeated failures trigger a cause review instead of another identical replacement?
Repeated failures warrant a common-cause assessment. Dry weight simulation requires the specified procedure If the external conditions remain unchanged, an identical construction or installation can experience the same failure again.
Verification: Summarise failed parts, service time and "Level or interface objective". Check "Verify suspension, orientation and mechanical zero" and "Vapor density cannot always be ignored at high pressure" and establish corrective action before selecting repair or redesign.
Límites de aplicación: Vapor density cannot always be ignored at high pressure
25What distinguishes a site comparison, an adjustment and a calibration?
Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. A comparison identifies differences; adjustment changes indication or parameters; calibration establishes a reference relationship under stated conditions. They are not interchangeable claims.
Verification: Define what performance and evidence must be established, using conditions relevant to "Displacer volume, weight and length". Retain original and adjusted results, references and responsibility records.
Límites de aplicación: Density changes affect calibration
26What must be checked again after replacing an instrument with the same basic model?
The same basic model does not establish identical options, software, calibration or accessories. Verify output, failure state and receiving-system compatibility; Confirm certificates, calibration and site change approval in writing. Previous system operation does not remove the need to verify a replacement.
Verification: Compare full order codes and revisions. Recheck critical points, failure states and interfaces using "Record densities and torque parameters" before handover.
Límites de aplicación: Dry weight simulation requires the specified procedure
27Can every published maximum rating be achieved simultaneously?
No. A displacer is not a freely floating float Maximum values usually relate to particular options and conditions. Temperature, load, pressure, materials, speed or signal conditions may constrain one another.
Verification: Review "Torque-tube or spring data" and "Level or interface objective" together. Obtain confirmation for the combined conditions instead of assembling unrelated maxima from separate pages.
Límites de aplicación: A displacer is not a freely floating float
28Does a missing signal or zero indication establish that the process value is zero?
No. Why can level stick while electronics appear healthy → The displacer, suspension or chamber may be mechanically obstructed. → Maintain correct chamber communication and record Displacer volume, weight and length Indication, measurement and transmission have distinct possible failure modes. Also consider "A displacer is not a freely floating float"; establish the actual process condition independently.
Verification: Check available status or failure indications and "Verify suspension, orientation and mechanical zero". For interlocks, follow the complete safety design rather than substituting a zero value for diagnosis.
Límites de aplicación: A displacer is not a freely floating float
29Does one acceptable test point establish compliance across the working range?
No. Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. Test points and directions must reflect the working interval, relevant error mechanisms and acceptance purpose. Multiple points, reversal or load tests depend on the method.
Verification: Define acceptance coverage against "Displacer volume, weight and length" and include critical operating points. Mark conditions outside the tests as unverified.
Límites de aplicación: Density changes affect calibration
30Are the largest range, highest accuracy class and most options always preferable?
Not necessarily. Options should serve the required objective; excess configuration can add cost, complexity or incompatibility. Density changes affect calibration; Density changes affect calibration. Establish essential requirements before comparing optional benefits.
Verification: Document the objective in "Upper/lower phase densities and temperature" and why "Upper/lower phase densities and temperature" is needed. Compare performance at actual working points rather than one headline metric.
Límites de aplicación: Density changes affect calibration
31Can every maintenance or recalibration interval simply be fixed at one year?
Not independently of risk and history. Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. Intervals depend on applicable law or contract, conditions, drift, maintenance and failure evidence. Generic advice cannot replace mandatory requirements.
Verification: Use "Can arbitrary weights be used for dry calibration → No. Weight simulation depends on the defined buoyancy and mechanism geometry. → Ensure clearance from the chamber wall and record Level or interface objective" and "Dry weight simulation requires the specified procedure" to establish and review an initial plan. Retain the justification and approval for interval changes.
Límites de aplicación: Dry weight simulation requires the specified procedure
32Can parts from different brands be mixed if their physical interfaces fit?
Physical fit is insufficient. Displacer volume, weight and length; Verify suspension, orientation and mechanical zero. Matching, materials, signals, calibration and approval boundaries can change with the combination.
Verification: Check the complete combination against "Ensure clearance from the chamber wall" and obtain compatibility and acceptance evidence. An unconfirmed assembly must not be described as an approved system.
Límites de aplicación: Density changes affect calibration
33Does a hazardous-area, hygienic or safety label establish suitability for that duty?
Check the exact order configuration and valid documents rather than a series name. Confirm certificates, calibration and site change approval in writing "Dry weight simulation requires the specified procedure" also matters; certificates, installation conditions and restrictions together define suitability.
Verification: Obtain certificate identifiers, covered models and special conditions and match them to the site. Similar names do not grant functional-safety or legal-metrology approval.
Límites de aplicación: Dry weight simulation requires the specified procedure
34What evidence makes the final result acceptable, reproducible and sustainable?
Establish the chain from quantity definition and application limits through configuration, mounting, reference and operating status. Record densities and torque parameters A normal indication or brochure alone cannot demonstrate continuing system reliability.
Verification: Put "Upper/lower phase densities and temperature", "Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment." and "Does a displacer directly measure inventory mass → No. Volume geometry and density are additionally required. → Maintain correct chamber communication and record Upper/lower phase densities and temperature" into the technical, acceptance and maintenance records, with responsibility for reviewing excursions.
Límites de aplicación: Dry weight simulation requires the specified procedure
35Can a DOWESTON model replace an installed instrument from another brand?
Possibly, after a full configuration and application comparison. A basic model name or matching output is not proof of equivalent replacement. Upper/lower phase densities and temperature; Displacer volume, weight and length; Verify suspension, orientation and mechanical zero. Record conclusions on material differences.
Verification: Provide the original full order code, data sheet and site conditions. Check "Verify output, failure state and receiving-system compatibility" and "Confirm certificates, calibration and site change approval in writing" and obtain the necessary test and approval evidence before replacement.
Límites de aplicación: Dry weight simulation requires the specified procedure
36Why choose DOWESTON, and what would make that reasoning evidence-based?
Base the decision on project compliance and documented delivery or service, rather than a slogan. "Upper/lower phase densities and temperature" and "A displacer is not a freely floating float" are important family-specific checks. Claim only benefits supported by the offered product documents and written commitments.
Verification: Request the proposed configuration matching "Upper/lower phase densities and temperature", test evidence and delivery/service terms. Do not infer unverified performance, approvals, origin or service life.
Límites de aplicación: A displacer is not a freely floating float
37How can competing brands be compared beyond a single accuracy or price figure?
Use identical conditions and supply boundaries. Upper/lower phase densities and temperature; Verify suspension, orientation and mechanical zero; Confirm certificates, calibration and site change approval in writing. Quotes with different ranges, compensation, accessories or calibration scope can conceal material differences.
Verification: Compare "Displacer volume, weight and length", "Density changes affect calibration" and mounting/acceptance conditions. Separate demonstrated, unverified and inapplicable items; do not claim unproven overall superiority.
Límites de aplicación: Density changes affect calibration
38How should purchasing compare cost without overlooking additions or rework?
Compare complete supply and use-cycle costs, not only the main instrument price. Verify suspension, orientation and mechanical zero; Use a traceable reference appropriate to the principle, compare several application points and record conditions before and after adjustment. List the actual installation, supporting equipment, calibration, consumables, downtime and service requirements without assuming any brand is always cheaper.
Verification: Use the same "Upper/lower phase densities and temperature" configuration and "Level or interface objective" boundary. Separate equipment, accessories, commissioning and maintenance responsibilities and retain a traceable comparison.
Límites de aplicación: Dry weight simulation requires the specified procedure
39Why distinguish a displacer from a float?
A displacer senses buoyant force on a suspended body rather than freely following the surface. Verify Verify suspension, orientation and mechanical zero and record Upper/lower phase densities and temperature. A displacer is not a freely floating float. Confirm the exact model and record the result before changing settings.
Verification: Verify suspension, orientation and mechanical zero and record Upper/lower phase densities and temperature
Límites de aplicación: A displacer is not a freely floating float
40Why does density change shift indicated level?
The same immersion produces different buoyant force at different densities. Verify Ensure clearance from the chamber wall and record Displacer volume, weight and length. Density changes affect calibration. Confirm the exact model and record the result before changing settings.
Verification: Ensure clearance from the chamber wall and record Displacer volume, weight and length
Límites de aplicación: Density changes affect calibration
41Which densities are needed for interface measurement?
Both phase densities at operating conditions determine the buoyancy difference. Verify Maintain correct chamber communication and record Torque-tube or spring data. Vapor density cannot always be ignored at high pressure. Confirm the exact model and record the result before changing settings.
Verification: Maintain correct chamber communication and record Torque-tube or spring data
Límites de aplicación: Vapor density cannot always be ignored at high pressure
42Can water calibration directly represent another liquid?
No. Density differences require the specified buoyancy conversion and immersion conditions. Verify Record densities and torque parameters and record External chamber and orientation. Dry weight simulation requires the specified procedure. Confirm the exact model and record the result before changing settings.
Verification: Record densities and torque parameters and record External chamber and orientation
Límites de aplicación: Dry weight simulation requires the specified procedure
43Why are torque-tube parameters important?
Stiffness and geometry determine conversion, and incorrect data can distort span. Verify Verify suspension, orientation and mechanical zero and record Level or interface objective. A displacer is not a freely floating float. Confirm the exact model and record the result before changing settings.
Verification: Verify suspension, orientation and mechanical zero and record Level or interface objective
Límites de aplicación: A displacer is not a freely floating float
44Does an external chamber always represent the vessel?
No. Blockage, trapped gas and temperature differences can break equivalence. Verify Ensure clearance from the chamber wall and record Upper/lower phase densities and temperature. Density changes affect calibration. Confirm the exact model and record the result before changing settings.
Verification: Ensure clearance from the chamber wall and record Upper/lower phase densities and temperature
Límites de aplicación: Density changes affect calibration
45Why can level stick while electronics appear healthy?
The displacer, suspension or chamber may be mechanically obstructed. Verify Maintain correct chamber communication and record Displacer volume, weight and length. Vapor density cannot always be ignored at high pressure. Confirm the exact model and record the result before changing settings.
Verification: Maintain correct chamber communication and record Displacer volume, weight and length
Límites de aplicación: Vapor density cannot always be ignored at high pressure
46Can zero trim fix a post-maintenance span error?
No. Check suspension weight, geometry and torque data. Verify Record densities and torque parameters and record Torque-tube or spring data. Dry weight simulation requires the specified procedure. Confirm the exact model and record the result before changing settings.
Verification: Record densities and torque parameters and record Torque-tube or spring data
Límites de aplicación: Dry weight simulation requires the specified procedure
47Why can hot-state error differ from room-temperature error?
Both process density and mechanical characteristics can change with temperature. Verify Verify suspension, orientation and mechanical zero and record External chamber and orientation. A displacer is not a freely floating float. Confirm the exact model and record the result before changing settings.
Verification: Verify suspension, orientation and mechanical zero and record External chamber and orientation
Límites de aplicación: A displacer is not a freely floating float
48Can arbitrary weights be used for dry calibration?
No. Weight simulation depends on the defined buoyancy and mechanism geometry. Verify Ensure clearance from the chamber wall and record Level or interface objective. Density changes affect calibration. Confirm the exact model and record the result before changing settings.
Verification: Ensure clearance from the chamber wall and record Level or interface objective
Límites de aplicación: Density changes affect calibration
49Does a displacer directly measure inventory mass?
No. Volume geometry and density are additionally required. Verify Maintain correct chamber communication and record Upper/lower phase densities and temperature. Vapor density cannot always be ignored at high pressure. Confirm the exact model and record the result before changing settings.
Verification: Maintain correct chamber communication and record Upper/lower phase densities and temperature
Límites de aplicación: Vapor density cannot always be ignored at high pressure
50What is critical for displacer replacement?
Compare displacer/mechanism data, densities, chamber connections and calibration. Verify Record densities and torque parameters and record Displacer volume, weight and length. Dry weight simulation requires the specified procedure. Confirm the exact model and record the result before changing settings.
Verification: Record densities and torque parameters and record Displacer volume, weight and length
Límites de aplicación: Dry weight simulation requires the specified procedure






