La edición en español aún no está disponible. A continuación se muestra la versión completa en inglés.
← Volver a la base de conocimientosEddy-current displacement probes: 50 selection, application and maintenance questions
50 shared questions for Eddy-current displacement probes, covering selection, delivery, maintenance, common questions and evidence-based brand comparisons, with verification actions, limits and sources.
Guarde sus referencias técnicas
Guarde un borrador en este navegador e impórtelo manualmente en Mi biblioteca después de iniciar sesión.
La cuenta sigue el proceso habitual de registro y aprobación. Guardar recursos no habilita automáticamente el acceso a precios u otros permisos comerciales.
Shared guidance for this product family. Confirm the complete model and application; family-level guidance is not evidence of a particular product specification or approval.
Use los principios generales junto con la validación del modelo. El rendimiento, las homologaciones y las alternativas dependen del código de pedido completo y las condiciones reales.
1What does the Eddy-current displacement probes principle establish, and what does it not establish?
An eddy-current probe senses conductive-target gap through changes caused by induced currents. Probe, extension and driver form a specified system, often measuring relative shaft vibration or position. The principle explains signal generation; it does not establish the range, accuracy, materials or approvals of every model. Review the physical principle and the application limits separately.
Verification: Confirm "Whether the target is static gap, shaft position or relative vibration" and assess "Sensitivity depends on target and system combination, not probe diameter alone" against the actual application. Record the complete model and document revision used.
Límites de aplicación: Sensitivity depends on target and system combination, not probe diameter alone
2Is the required result measured directly or calculated from other inputs?
Define the quantity to be accepted before selecting a display unit. An eddy-current probe senses conductive-target gap through changes caused by induced currents. Probe, extension and driver form a specified system, often measuring relative shaft vibration or position. For "Whether the target is static gap, shaft position or relative vibration", document output definitions and conversion or compensation conditions; displaying a value does not make it a direct measurement under all conditions.
Verification: Document the process objective, units and reference conditions. Check "Mixing system parts merely because connectors fit" and list separate inputs and acceptance methods for calculated results.
Límites de aplicación: Mixing system parts merely because connectors fit
3Which application information is needed before requesting a quotation?
Prepare at least these five input groups: Whether the target is static gap, shaft position or relative vibration; Target material, geometry, surface and available area; Total electrical length and probe/driver matching; Working gap, displacement range, temperature and speed; Monitor interface, bias and alarm/protection duty. Mark unknown items for confirmation instead of substituting a normal point or an assumed default for all conditions.
Verification: Have process, instrumentation and purchasing roles agree the inputs, particularly "Target material, geometry, surface and available area". Resolve missing evidence before requesting application confirmation.
Límites de aplicación: Sensitivity depends on target and system combination, not probe diameter alone
4How should the range be chosen rather than copied from a nominal equipment rating?
Select the range from actual operating conditions and permissible error, then check extremes and installation constraints. For this family: Sensitivity depends on target and system combination, not probe diameter alone Nominal size or maximum equipment rating need not equal the useful measuring interval.
Verification: List minimum, normal, maximum and abnormal conditions. Check "Total electrical length and probe/driver matching" against the documented performance envelope.
Límites de aplicación: Sensitivity depends on target and system combination, not probe diameter alone
5Can a larger turndown claim or display rescaling fix poor low-end performance?
No. Low-end usability depends on the principle, available signal and error mechanisms. DC gap must lie in the linear range with dynamic headroom More display digits, software scaling or a stated turndown cannot remove the original noise or installation error.
Verification: Obtain error definitions and limits at the actual low operating point. Use "Scale error: check target, system length and sensitivity" to investigate bias instead of comparing only percent-of-full-scale values.
Límites de aplicación: DC gap must lie in the linear range with dynamic headroom
6How should compatibility with the measured object and materials be established?
Use the complete measured object and actual exposure, rather than a material name alone. Working gap, displacement range, temperature and speed Avoid this family-specific misuse: Substituting a DC gap check for dynamic verification For non-wetted equipment, assess loads, target materials, signals and environmental compatibility instead.
Verification: List the actual contact or loading parts, seals, insulation and cleaning conditions. Have the responsible parties assess "Electrical target runout can combine with mechanical runout".
Límites de aplicación: Electrical target runout can combine with mechanical runout
7Why must abnormal and environmental conditions be listed separately from normal operation?
Normal measurement, temporary excursions and survival limits are different requirements. Electrical target runout can combine with mechanical runout Start-up, cleaning, impacts, power interruption or abnormal environments can determine the necessary construction and protection.
Verification: Complete the worst-case conditions using "Monitor interface, bias and alarm/protection duty" and check "Relative shaft vibration is not automatically absolute casing vibration". Separate continuous operating limits from temporary limits in the specification.
Límites de aplicación: Relative shaft vibration is not automatically absolute casing vibration
8Can the published instrument accuracy be used as the installed system accuracy?
Not without assessment. Establish a static displacement curve with the matched system and representative target, then verify required dynamics; do not transfer calibration from another material or electrical length without evidence. The installed system also includes object, mounting, signal conversion, environmental and reference effects. Derived results additionally depend on the relevant input uncertainties.
Verification: Agree actual test points, installation conditions and the acceptance reference. Check "Use matched probe/cable/driver and the specified total length" and document the system error or uncertainty basis.
Límites de aplicación: DC gap must lie in the linear range with dynamic headroom
9How should response time, filtering and a stable display be balanced?
A stable indication and fast change detection involve a trade-off; filtering cannot repair incorrect installation or real process variation. Speed-related anomaly: distinguish mechanical/electrical runout and real vibration Review the complete chain when fast response matters, not merely the display refresh rate.
Verification: Define the shortest relevant event and acceptable delay. Check "Set bias from the static gap curve and verify full-motion linearity" and verify local output, display and receiving-system response using a controlled change.
Límites de aplicación: Treating all electrical runout as real shaft motion
10Which typical applications fit, and which require a specific engineering review?
Typical contexts include: Relative shaft-vibration monitoring; Axial-position and gap trending; Non-contact displacement tests on conductive targets. Similar application labels do not establish equivalent conditions. In particular, assess "Relative shaft vibration is not automatically absolute casing vibration" before relying on another installation as proof.
Verification: Select the nearest application and compare "Whether the target is static gap, shaft position or relative vibration" and "Monitor interface, bias and alarm/protection duty". Obtain written confirmation where published application limits are exceeded.
Límites de aplicación: Relative shaft vibration is not automatically absolute casing vibration
11How should a complete order code be defined without unspecified standard options?
Translate required functions, performance and physical interfaces into verifiable options. Probe, extension, driver family and total electrical length; Target material, diameter, surface and temperature. Options affecting suitability or supply scope should be explicit; terms such as standard or same as existing are insufficient.
Verification: Check the complete order code and selection sheet, especially "Total electrical length and probe/driver matching". List accessories, documents, calibration and delivery boundaries separately.
Límites de aplicación: Mixing system parts merely because connectors fit
12Which mounting and mechanical layout checks belong before ordering?
Use matched probe/cable/driver and the specified total length The installation drawing must match the available space and process or mechanical structure. Access for fitting and servicing should be established before delivery.
Verification: Review a dimensioned, oriented site drawing. Use "Working gap, displacement range, temperature and speed" and "Electrical target runout can combine with mechanical runout" to confirm connections, support, removal access and safe isolation.
Límites de aplicación: Electrical target runout can combine with mechanical runout
13How can supporting infrastructure prevent an instrument that fits but cannot be used?
Mount probe/support with the required target and nearby-metal clearances Supporting conditions are part of the measurement system. Matching mechanical connections or signal names alone do not establish power, I/O, grounding or configuration compatibility.
Verification: Confirm "Sensitivity, linear gap and dynamic range" and "Monitor interface, supply and failure state" against actual terminals, loops and receiving-system settings.
Límites de aplicación: Substituting a DC gap check for dynamic verification
14What is a sensible commissioning sequence before changing correction factors?
Check identity, installation and basic conditions first, then status, output and process response. Set bias from the static gap curve and verify full-motion linearity Preserve original evidence for unexplained anomalies instead of concealing them with zero or factor adjustments.
Verification: Record factory settings and initial status. Investigate "No valid gap: inspect power, connectors, matching and range" step by step and change parameters only after identifying the cause and using an authorised procedure.
Límites de aplicación: Treating all electrical runout as real shaft motion
15Do identical output units or interface names establish connection compatibility?
No. Establish the represented object and reference conditions: Probe, extension, driver family and total electrical length. Electrical equipment also needs loop type, scaling, failure behaviour and protocol details checked. Mechanical indicators require clear boundaries between indication and remote-transmission accessories.
Verification: Check the receiving-system variable against "Whether the target is static gap, shaft position or relative vibration" and verify limits, units and abnormal states with the actual equipment. Record wiring, configuration and end-to-end checks against "Mount probe/support with the required target and nearby-metal clearances".
Límites de aplicación: Substituting a DC gap check for dynamic verification
16What should a calibration report contain to be relevant to the application?
Establish a static displacement curve with the matched system and representative target, then verify required dynamics; do not transfer calibration from another material or electrical length without evidence. The report should identify the delivered instrument, measured quantity, conditions, method and results. A general conformity certificate does not establish performance for every option or operating condition.
Verification: Check serial number, points, units, reference equipment and traceability. Compare "Target material, geometry, surface and available area" with the calibrated conditions and agree separate acceptance where they differ.
Límites de aplicación: DC gap must lie in the linear range with dynamic headroom
17How can delivery and site acceptance use reproducible pass criteria?
Verify raw voltage, monitor scaling and shaft-position reference Agree criteria before testing, including range, conditions, error definition and treatment of anomalies. Similar-looking readings or an unsuitable portable reference are not sufficient acceptance evidence.
Verification: Choose an appropriate reference using "Establish a static displacement curve with the matched system and representative target, then verify required dynamics; do not transfer calibration from another material or electrical length without evidence.". Record "Whether the target is static gap, shaft position or relative vibration" and test conditions; investigate "Scale error: check target, system length and sensitivity" before deciding on rework or recalibration.
Límites de aplicación: DC gap must lie in the linear range with dynamic headroom
18What belongs in the quotation and agreement for a non-standard application?
Define why the standard supply is insufficient, the required verification and the responsible parties. Relative shaft vibration is not automatically absolute casing vibration; Disconnecting probes or bypassing protection arbitrarily on a running machine. Additional materials, construction, documents or tests depend on actual requirements.
Verification: Attach "Monitor interface, bias and alarm/protection duty" and the deviations. Obtain technical confirmation, additional charges, delivery conditions and acceptance methods; unknown requirements must not be assumed satisfied.
Límites de aplicación: Relative shaft vibration is not automatically absolute casing vibration
19Where should investigation start when there is no valid reading or output?
No valid gap: inspect power, connectors, matching and range Distinguish the actual measured condition from device-state and readout or transmission faults. Do not immediately interpret missing data as sensor failure or a zero process value.
Verification: Under appropriate safe isolation, check "Mount probe/support with the required target and nearby-metal clearances". Compare local and receiving-end status and record when the fault appeared.
Límites de aplicación: Mixing system parts merely because connectors fit
20How can unstable readings be separated from genuine process variation?
Speed-related anomaly: distinguish mechanical/electrical runout and real vibration Compare independent process evidence and raw signals before deciding whether installation, interference or equipment is responsible. More filtering can hide a real abnormal event.
Verification: Keep conditions comparable and record correlation with process or equipment events. Check "Use matched probe/cable/driver and the specified total length" and change one factor at a time.
Límites de aplicación: Treating all electrical runout as real shaft motion
21How should a persistent high or low bias be investigated before changing factors?
Scale error: check target, system length and sensitivity Systematic bias can arise from units, reference conditions, configuration, installation or the reference method. An unexplained correction can move one operating-point error to other conditions.
Verification: Align quantities, time bases and units first. Review the reference using "Establish a static displacement curve with the matched system and representative target, then verify required dynamics; do not transfer calibration from another material or electrical length without evidence." and confirm that "Target material, geometry, surface and available area" matches the configuration.
Límites de aplicación: DC gap must lie in the linear range with dynamic headroom
22When is it appropriate to adjust a drifting zero or reference position?
Slow baseline shift: inspect thermal motion, support and static bias Establish a genuine, stable reference condition that meets the method requirements before considering adjustment. Some instruments have no freely adjustable site zero.
Verification: Check "Set bias from the static gap curve and verify full-motion linearity" and "Establish a static displacement curve with the matched system and representative target, then verify required dynamics; do not transfer calibration from another material or electrical length without evidence." and retain before-and-after results. If the conditions cannot be established, remove external effects or use a qualified service.
Límites de aplicación: Treating all electrical runout as real shaft motion
23Which evidence helps diagnose intermittent alarms or failures?
Intermittent invalidity: inspect contact, cable damage and gap excursions Intermittent faults need correlated event records, not just a normal display after recovery. Review alarm settings, communication status and actual process abnormalities separately.
Verification: Retain time, status codes, raw trends and the contemporaneous "Monitor interface, bias and alarm/protection duty". Compare "Mount probe/support with the required target and nearby-metal clearances" and "Set bias from the static gap curve and verify full-motion linearity" to locate the failing link.
Límites de aplicación: Disconnecting probes or bypassing protection arbitrarily on a running machine
24Why should repeated failures trigger a cause review instead of another identical replacement?
Repeated failures warrant a common-cause assessment. Disconnecting probes or bypassing protection arbitrarily on a running machine If the external conditions remain unchanged, an identical construction or installation can experience the same failure again.
Verification: Summarise failed parts, service time and "Monitor interface, bias and alarm/protection duty". Check "Use matched probe/cable/driver and the specified total length" and "Electrical target runout can combine with mechanical runout" and establish corrective action before selecting repair or redesign.
Límites de aplicación: Electrical target runout can combine with mechanical runout
25What distinguishes a site comparison, an adjustment and a calibration?
Establish a static displacement curve with the matched system and representative target, then verify required dynamics; do not transfer calibration from another material or electrical length without evidence. A comparison identifies differences; adjustment changes indication or parameters; calibration establishes a reference relationship under stated conditions. They are not interchangeable claims.
Verification: Define what performance and evidence must be established, using conditions relevant to "Target material, geometry, surface and available area". Retain original and adjusted results, references and responsibility records.
Límites de aplicación: DC gap must lie in the linear range with dynamic headroom
26What must be checked again after replacing an instrument with the same basic model?
The same basic model does not establish identical options, software, calibration or accessories. Monitor interface, supply and failure state; Machine, hazardous-area and protection-function documentation. Previous system operation does not remove the need to verify a replacement.
Verification: Compare full order codes and revisions. Recheck critical points, failure states and interfaces using "Verify raw voltage, monitor scaling and shaft-position reference" before handover.
Límites de aplicación: Disconnecting probes or bypassing protection arbitrarily on a running machine
27Can every published maximum rating be achieved simultaneously?
No. Sensitivity depends on target and system combination, not probe diameter alone Maximum values usually relate to particular options and conditions. Temperature, load, pressure, materials, speed or signal conditions may constrain one another.
Verification: Review "Total electrical length and probe/driver matching" and "Monitor interface, bias and alarm/protection duty" together. Obtain confirmation for the combined conditions instead of assembling unrelated maxima from separate pages.
Límites de aplicación: Sensitivity depends on target and system combination, not probe diameter alone
28Does a missing signal or zero indication establish that the process value is zero?
No. No valid gap: inspect power, connectors, matching and range Indication, measurement and transmission have distinct possible failure modes. Also consider "Mixing system parts merely because connectors fit"; establish the actual process condition independently.
Verification: Check available status or failure indications and "Sensitivity, linear gap and dynamic range". For interlocks, follow the complete safety design rather than substituting a zero value for diagnosis.
Límites de aplicación: Mixing system parts merely because connectors fit
29Does one acceptable test point establish compliance across the working range?
No. Establish a static displacement curve with the matched system and representative target, then verify required dynamics; do not transfer calibration from another material or electrical length without evidence. Test points and directions must reflect the working interval, relevant error mechanisms and acceptance purpose. Multiple points, reversal or load tests depend on the method.
Verification: Define acceptance coverage against "Target material, geometry, surface and available area" and include critical operating points. Mark conditions outside the tests as unverified.
Límites de aplicación: DC gap must lie in the linear range with dynamic headroom
30Are the largest range, highest accuracy class and most options always preferable?
Not necessarily. Options should serve the required objective; excess configuration can add cost, complexity or incompatibility. DC gap must lie in the linear range with dynamic headroom; Substituting a DC gap check for dynamic verification. Establish essential requirements before comparing optional benefits.
Verification: Document the objective in "Whether the target is static gap, shaft position or relative vibration" and why "Probe, extension, driver family and total electrical length" is needed. Compare performance at actual working points rather than one headline metric.
Límites de aplicación: DC gap must lie in the linear range with dynamic headroom
31Can every maintenance or recalibration interval simply be fixed at one year?
Not independently of risk and history. Establish a static displacement curve with the matched system and representative target, then verify required dynamics; do not transfer calibration from another material or electrical length without evidence. Intervals depend on applicable law or contract, conditions, drift, maintenance and failure evidence. Generic advice cannot replace mandatory requirements.
Verification: Use "Slow baseline shift: inspect thermal motion, support and static bias" and "Disconnecting probes or bypassing protection arbitrarily on a running machine" to establish and review an initial plan. Retain the justification and approval for interval changes.
Límites de aplicación: Disconnecting probes or bypassing protection arbitrarily on a running machine
32Can parts from different brands be mixed if their physical interfaces fit?
Physical fit is insufficient. Target material, diameter, surface and temperature; Sensitivity, linear gap and dynamic range. Matching, materials, signals, calibration and approval boundaries can change with the combination.
Verification: Check the complete combination against "Mount probe/support with the required target and nearby-metal clearances" and obtain compatibility and acceptance evidence. An unconfirmed assembly must not be described as an approved system.
Límites de aplicación: Substituting a DC gap check for dynamic verification
33Does a hazardous-area, hygienic or safety label establish suitability for that duty?
Check the exact order configuration and valid documents rather than a series name. Machine, hazardous-area and protection-function documentation "Relative shaft vibration is not automatically absolute casing vibration" also matters; certificates, installation conditions and restrictions together define suitability.
Verification: Obtain certificate identifiers, covered models and special conditions and match them to the site. Similar names do not grant functional-safety or legal-metrology approval.
Límites de aplicación: Relative shaft vibration is not automatically absolute casing vibration
34What evidence makes the final result acceptable, reproducible and sustainable?
Establish the chain from quantity definition and application limits through configuration, mounting, reference and operating status. Verify raw voltage, monitor scaling and shaft-position reference A normal indication or brochure alone cannot demonstrate continuing system reliability.
Verification: Put "Whether the target is static gap, shaft position or relative vibration", "Establish a static displacement curve with the matched system and representative target, then verify required dynamics; do not transfer calibration from another material or electrical length without evidence." and "Intermittent invalidity: inspect contact, cable damage and gap excursions" into the technical, acceptance and maintenance records, with responsibility for reviewing excursions.
Límites de aplicación: Relative shaft vibration is not automatically absolute casing vibration
35Can a DOWESTON model replace an installed instrument from another brand?
Possibly, after a full configuration and application comparison. A basic model name or matching output is not proof of equivalent replacement. Probe, extension, driver family and total electrical length; Target material, diameter, surface and temperature; Sensitivity, linear gap and dynamic range. Record conclusions on material differences.
Verification: Provide the original full order code, data sheet and site conditions. Check "Monitor interface, supply and failure state" and "Machine, hazardous-area and protection-function documentation" and obtain the necessary test and approval evidence before replacement.
Límites de aplicación: Relative shaft vibration is not automatically absolute casing vibration
36Why choose DOWESTON, and what would make that reasoning evidence-based?
Base the decision on project compliance and documented delivery or service, rather than a slogan. "Whether the target is static gap, shaft position or relative vibration" and "Sensitivity depends on target and system combination, not probe diameter alone" are important family-specific checks. Claim only benefits supported by the offered product documents and written commitments.
Verification: Request the proposed configuration matching "Probe, extension, driver family and total electrical length", test evidence and delivery/service terms. Do not infer unverified performance, approvals, origin or service life.
Límites de aplicación: Sensitivity depends on target and system combination, not probe diameter alone
37How can competing brands be compared beyond a single accuracy or price figure?
Use identical conditions and supply boundaries. Probe, extension, driver family and total electrical length; Sensitivity, linear gap and dynamic range; Machine, hazardous-area and protection-function documentation. Quotes with different ranges, compensation, accessories or calibration scope can conceal material differences.
Verification: Compare "Target material, geometry, surface and available area", "DC gap must lie in the linear range with dynamic headroom" and mounting/acceptance conditions. Separate demonstrated, unverified and inapplicable items; do not claim unproven overall superiority.
Límites de aplicación: DC gap must lie in the linear range with dynamic headroom
38How should purchasing compare cost without overlooking additions or rework?
Compare complete supply and use-cycle costs, not only the main instrument price. Use matched probe/cable/driver and the specified total length; Establish a static displacement curve with the matched system and representative target, then verify required dynamics; do not transfer calibration from another material or electrical length without evidence. List the actual installation, supporting equipment, calibration, consumables, downtime and service requirements without assuming any brand is always cheaper.
Verification: Use the same "Probe, extension, driver family and total electrical length" configuration and "Monitor interface, bias and alarm/protection duty" boundary. Separate equipment, accessories, commissioning and maintenance responsibilities and retain a traceable comparison.
Límites de aplicación: Relative shaft vibration is not automatically absolute casing vibration
39Can a probe be used with any driver if the connector fits?
No. Coil characteristics, electrical length, compensation and sensitivity are a system design; unmatched parts can be nonlinear or invalid.
Verification: Check complete part numbers and the permitted matching table and verify a representative target curve.
Límites de aplicación: Sensitivity depends on target and system combination, not probe diameter alone
40Is system electrical length just any added physical cable length?
No. The system uses specified probe/extension combinations and cable properties. Adding generic cable to a stated metre length does not establish matching.
Verification: Check permitted cables and lengths and reverify static linearity and sensitivity after changes.
Límites de aplicación: DC gap must lie in the linear range with dynamic headroom
41Why can different target metals produce different sensitivity?
Conductivity and magnetic properties alter eddy-current response; curvature and target size also matter. A target-specific curve is not universal.
Verification: Identify actual shaft material and relevant treatment and verify with representative material or an approved method.
Límites de aplicación: Electrical target runout can combine with mechanical runout
42Does operating near the static-gap range edge affect vibration measurement?
Yes. Dynamic motion may leave the linear range and clip or distort even if the average gap is displayed. Allow for vibration and thermal movement.
Verification: Record cold/hot gap and peak motion and verify the complete instantaneous gap remains linear.
Límites de aplicación: Relative shaft vibration is not automatically absolute casing vibration
43Does a slow-roll periodic signal always indicate shaft bending?
No. Material, magnetism or surface treatment can cause electrical runout, while geometric eccentricity causes mechanical runout; distinguish both from operating vibration.
Verification: Compare slow-roll, mechanical and operating evidence using the machine’s approved procedure.
Límites de aplicación: Sensitivity depends on target and system combination, not probe diameter alone
44What does insufficient probe-bracket stiffness change?
The probe measures its gap to the target, so bracket movement or resonance enters the signal. Static firmness does not establish dynamic stiffness.
Verification: Inspect bracket construction and fastening and assess band response against independent evidence.
Límites de aplicación: DC gap must lie in the linear range with dynamic headroom
45Can a probe’s DC output be treated as a generic 0–10 V signal?
Do not assume that. Polarity, bias, range, impedance and fault states are system-specific, and monitors may use both DC gap and AC motion.
Verification: Check driver/monitor terminals, polarity and scaling and verify with an approved simulation method.
Límites de aplicación: Electrical target runout can combine with mechanical runout
46Do two radial probes automatically provide a correct shaft orbit?
Correct orientation, angle, polarity, synchronisation and reference are required; support motion and runout also affect the orbit. Two values alone are insufficient.
Verification: Document geometry/timing and verify orbit direction and amplitude with known motion or an approved check.
Límites de aplicación: Relative shaft vibration is not automatically absolute casing vibration
47Does every axial-position change represent rotor movement?
The reading is relative to the probe; casing/support thermal growth and probe baseline can contribute. Interpret it using the machine’s reference definition.
Verification: Define the reference structure, correlate temperatures and state and inspect support and cold baseline.
Límites de aplicación: Sensitivity depends on target and system combination, not probe diameter alone
48How can a target edge or nearby metal affect a probe?
The field can interact with non-target metal, altering sensitivity, linearity or probe interaction. Meet target area, spacing and support-material requirements.
Verification: Check target area and metal clearances and verify with the actual geometry if necessary.
Límites de aplicación: DC gap must lie in the linear range with dynamic headroom
49Can a probe be unplugged on a running machine to test protection?
Do not do this arbitrarily. It can trip the machine or disable protection; use an approved test, bypass and restoration procedure controlled by the machine owner.
Verification: Define scope, operating conditions, authorisation and verified bypass restoration in the approved work plan.
Límites de aplicación: Electrical target runout can combine with mechanical runout
50Does a valid DC gap check prove shaft-vibration protection works?
No. A DC check does not cover dynamic sensitivity, bandwidth, monitor algorithms, delay or final actuation; validate the complete protection function.
Verification: List static, dynamic and alarm/actuation checks separately and retain approved test results.
Límites de aplicación: Relative shaft vibration is not automatically absolute casing vibration






