Start with your process. Find the right instrument.
Learn measurement principles, check process conditions, configure products and save technical resources.

A complete English edition of this article has not been published. The complete available Chinese version is shown below.

← Back to knowledge hub
Measuring principles4 min readContent language: ChineseUpdated 23 October 2026

4~20mA怎样换算雷达液位,为什么有时方向反了?

先确认电流对应液位、距离还是容积,再进行线性换算。

电流必须先有清楚的变量定义

4~20mA只是传递数值的方式,本身不说明传的是液位还是距离。若当前输出液位且为正向线性,过程值可按“下限+(电流−4)/16×跨度”换算。若设置为反向、非线性容积或其他变量,则不能直接套同一表达式。

示例只用于说明映射关系

假设4mA对应0米、20mA对应10米,则12mA对应5米;这不是任意罐的默认设置。雷达距离随液位升高而减小,若PLC把距离当作液位,画面就可能反向。故障电流还需作为异常处理,不能直接算成有效库存。

交付应保留回路对照表

让道威斯顿配置单与PLC表明确输出变量、单位、量程上下限和故障行为。调试时核对低、中、高几个点,分别记录电流、仪表显示和控制系统读数。三项一致后,再评估测量本身是否符合现场参照。

模拟量映射需要核对的四件事

线性公式只有在变量、端点和方向都确认后才可用,计算正确不代表输入条件已经正确。

  • 从配置中确认输出的是液位、距离还是线性化容积,核对变量单位,不只按画面名称或接线标记猜测。
  • 把电流下限、上限及工程量对应值写在同一行,说明正向或反向,检查仪表与PLC是否采用完全相同端点。
  • 确认故障电流、超量程和通信状态的处理规则,不能把异常电流继续换算成可信库存,也不能抹去设备诊断。
  • 在批准的测试条件下记录多个点的实际电流与工程值,验证结束后恢复正式设置,并让仪表和系统人员共同确认。

假设核对:两端跨度相同但变量不同

假设仪表输出天线到液面的距离,PLC却按液位进行同方向换算。液面升高时雷达距离缩短,电流变化在数学上完全符合仪表配置,但系统画面却朝相反方向走。应先决定需要在哪一端完成距离到液位的转换,再统一参考高度和输出定义,而不是靠反接线路或随意加补偿修正。测试时用已知过程状态确认趋势方向,再检查几个对应点。这个假设说明方向错误可以来自变量定义,模拟量回路有电流并不代表工程量含义一致。

Apply this knowledge to product selection

Customers and procurement

Check actual application and acceptance requirements against the article and product documentation. Bring open questions to DOWESTON for technical review.

Sales and technical teams

Record customer questions with application conditions. Verify range, interfaces and operating requirements against the selected model documentation.

Turn questions into application requirements

Collect application, connection, installation and acceptance requirements for the selected product, then review open points with DOWESTON.

Choose a product and prepare requirements
Not signed in to DOWESTON?
Create an account to start selecting products, check prices, and receive our newsletter on the latest products and trends.
Products & Services
Doweston offers a range of services to help you quickly build automated instrumentation systems. Contact us to learn more.
Ready to buy?
If you would like to purchase products,
simply contact our sales team — we are happy to help.
Who we are
DOWESTON delivers accurate and reliable measurement solutions
— trusted sensing and detection products for every industry!
Need service?
If you want to optimize production and reduce downtime,
we can help you choose the right spare parts and service products.
Edit Configuration

Product

Brand

Model

Confirm Changes Cancel
Your screen may be too small for the best experience.
We recommend using a computer,
or contact an engineer right away for selection support!
Need faster service? Call
400-888-4436
Continue Browsing