Start with your process. Find the right instrument.
Learn measurement principles, check process conditions, configure products and save technical resources.

A complete English edition of this article has not been published. The complete available Chinese version is shown below.

← Back to knowledge hub
Measuring principles4 min readContent language: ChineseUpdated 23 October 2026

隔离式安全栅:气组为何会改变同一安全栅的Co和Lo?

不同气组对点燃能量的约束不同,同一输出回路可能在不同气组下给出不同允许电容电感。

直接回答与技术机理

不同气组对点燃能量的约束不同,同一输出回路可能在不同气组下给出不同允许电容电感。数值必须与项目介质气组对应。

气组改变时,允许Co和Lo可能同时变化,而且组合表脚注仍然有效。不得只修改计算表标题而继续沿用旧数值。若项目介质条件未确定,应先补齐分类依据,再锁定相应参数组。同一气组下也可能有多个输出模式,气组匹配后仍不能跨模式取最大允许值。

成立条件和独立约束

不能因某组的表格余量大就借用,也不能只看外壳上的通用防爆字样忽略参数表。

核查重点是:不能借用另一气组较大Co或Lo。本安关联设备将非本安侧与危险侧回路分隔并限制规定条件下可输出的能量。

针对本题的核对方法

  • 先确定项目适用气组,再锁定证书同一气组的完整实体参数行。
  • 气组选择决定对应的允许参数。
  • 不能借用另一气组较大Co或Lo。
  • 对“项目要求更严格气组,工程人员若沿用另一气组较大的Co,线缆预算可能失去依据”记录实际端子、参数来源与观察条件;结合“不能因某组的表格余量大就借用,也不能只看外壳上的通用防爆字样忽略参数表”核对本题尚未验证的约束。

假设案例与判定

假设出现以下情况:项目要求更严格气组,工程人员若沿用另一气组较大的Co,线缆预算可能失去依据。

这一案例需采用前述参数定义和适用条件作判断,不能把正常功能、单项比较及整条回路的最终结论混为一项。若实际型号文件的条件与案例不同,应回到实际文件重新评价。此情景用于解释技术判据。

系统边界及所需证据

参数比较是特定方法下的技术判断,不是对现场作业的授权;本文不提供带电危险区接线或绕过保护的步骤。

复核所需技术对象包括:提供回路图、完整证书及控制图、现场设备参数、电缆附件清单和项目区域条件。参数必须来自实际订货型号及对应端子组,示例资料不构成道威斯顿产品能力承诺。图纸与证书所列条件不一致时,应先解决不一致,而不能按较有利的一份资料放行。

Apply this knowledge to product selection

Customers and procurement

Check actual application and acceptance requirements against the article and product documentation. Bring open questions to DOWESTON for technical review.

Sales and technical teams

Record customer questions with application conditions. Verify range, interfaces and operating requirements against the selected model documentation.

Turn questions into application requirements

Collect application, connection, installation and acceptance requirements for the selected product, then review open points with DOWESTON.

Choose a product and prepare requirements
Not signed in to DOWESTON?
Create an account to start selecting products, check prices, and receive our newsletter on the latest products and trends.
Products & Services
Doweston offers a range of services to help you quickly build automated instrumentation systems. Contact us to learn more.
Ready to buy?
If you would like to purchase products,
simply contact our sales team — we are happy to help.
Who we are
DOWESTON delivers accurate and reliable measurement solutions
— trusted sensing and detection products for every industry!
Need service?
If you want to optimize production and reduce downtime,
we can help you choose the right spare parts and service products.
Edit Configuration

Product

Brand

Model

Confirm Changes Cancel
Your screen may be too small for the best experience.
We recommend using a computer,
or contact an engineer right away for selection support!
Need faster service? Call
400-888-4436
Continue Browsing