Start with your process. Find the right instrument.
Learn measurement principles, check process conditions, configure products and save technical resources.

A complete English edition of this article has not been published. The complete available Chinese version is shown below.

← Back to knowledge hub
Measuring principles5 min readContent language: ChineseUpdated 23 October 2026

4~20 mA 压力信号在 PLC 中怎样换算,为什么 4 mA 不总是零压力?

电流下端对应所订量程下限,复合压力或非零下限必须按完整线性关系缩放。

Start an application checklist

使用上下限计算

对于明确为线性 4~20 mA 的配置,压力=下限+(电流-4 mA)÷16 mA×(上限-下限)。这是一条线性换算关系,应以订货量程为准。例如下限不是零时,4 mA 也不代表零压力;正负压复合量程尤其容易在这里设错。例如零到一兆帕量程在十二毫安时,对应半兆帕;这仍只是理想换算。

区分正常范围与异常信号

先核对采集卡原始数值的定义和量程,再做工程单位换算。不能把所有低于 4 mA 的值都强制当成零,也不能将高于 20 mA 的信号一律继续外推;超量程与故障状态如何处理,应查看传感器和卡件的具体文件。

用三点验证整个链路

调试时以量程下限、中间点和上限核对参考压力、实测电流、卡件原始值及画面压力。把四列数据交给道威斯顿,可以区分传感器输出问题和程序缩放问题。更换量程后还应同步检查报警与趋势单位,不能只修改画面数字。

现场核对:上下限与工程单位成套设置

  • 从铭牌或确认单读取所订量程下限、上限和压力参照,确认是否采用线性输出。
  • 核对卡件原始计数、电流范围和工程单位转换,检查是否重复缩放或遗漏偏置。
  • 在低、中、高点同时记录参考压力、原始信号、卡件数值和最终画面结果。
  • 报警、趋势、记录和通信使用同一已确认单位,并单独定义超范围与故障状态处理。

假设例子:复合量程的零压力位于电流范围中间

假设线性电流输出对应负一百到正一百千帕,下限为四毫安、上限为二十毫安,则零表压位于量程中点,对应十二毫安。若程序误将四毫安设置为零表压,整个显示就会错误偏移。该例只有理想线性数学关系,不代表实际产品的精度、量程或超范围行为。

销售可请客户用一个已知压力状态描述预期显示,再与公式对照,尤其注意负下限和非零下限。若电流正确但画面错误,应优先检查缩放和单位;若电流本身与参考不符,再检查回路和传感器。不要用调整硬件零点去抵消一段错误程序,否则更换或复校时问题会再次出现。

Apply this knowledge to product selection

Customers and procurement

Check actual application and acceptance requirements against the article and product documentation. Bring open questions to DOWESTON for technical review.

Sales and technical teams

Record customer questions with application conditions. Verify range, interfaces and operating requirements against the selected model documentation.

Turn questions into application requirements

Collect application, connection, installation and acceptance requirements for the selected product, then review open points with DOWESTON.

Start an application checklist
Not signed in to DOWESTON?
Create an account to start selecting products, check prices, and receive our newsletter on the latest products and trends.
Products & Services
Doweston offers a range of services to help you quickly build automated instrumentation systems. Contact us to learn more.
Ready to buy?
If you would like to purchase products,
simply contact our sales team — we are happy to help.
Who we are
DOWESTON delivers accurate and reliable measurement solutions
— trusted sensing and detection products for every industry!
Need service?
If you want to optimize production and reduce downtime,
we can help you choose the right spare parts and service products.
Edit Configuration

Product name

Brand

Model

Confirm Changes Cancel
Your screen may be too small for the best experience.
We recommend using a computer,
or contact an engineer right away for selection support!
Need faster service? Call
400-888-4436
Continue Browsing