The reference pressure is the difference
Gauge pressure is the difference between the absolute process pressure and local atmospheric pressure. Absolute pressure is measured relative to a perfect vacuum. With the process port open to the local atmosphere, a vented gauge sensor should read close to zero, while an absolute sensor should read close to the local atmospheric pressure. Even when both readings are expressed in bar or kPa, they cannot be compared directly. Specify the pressure type on the order.
Choose according to the control objective
For pneumatic or hydraulic equipment where pressure relative to the surroundings matters, start by evaluating a gauge-pressure sensor. Vacuum processes and gas-state calculations that require absolute pressure should use an absolute sensor or a conversion method that has been justified. Adding a fixed atmospheric pressure in the program does not make the results equivalent at different elevations or under different weather conditions.
Keep the reference consistent when replacing an instrument
Give Doweston the old nameplate details, the control objective, the installation site and the PLC range settings. In particular, clarify whether “zero pressure” means vented to atmosphere or evacuated. During commissioning, compare the reference instrument and the sensor under test using the same pressure reference before assessing zero offset. Do not adjust zero solely because the readout is above or below zero.
Field checks: define the pressure reference first
- State gauge or absolute pressure in the process documentation and verify that the original instrument, the reference instrument and the program use the same reference.
- Record the expected readings when vented, during normal operation and under vacuum. Check what “zero pressure” means in each case.
- For gas-state calculations, check whether the formula requires absolute pressure before using a gauge reading.
- For equipment used at several sites, document whether local elevation and atmospheric changes affect the required result. Check other sources of error, such as temperature, separately.
Example: a difference of one atmosphere may be normal
Suppose a customer replaces a gauge sensor with an absolute sensor of the same numerical range. The new sensor does not read zero with the port vented. If the local atmospheric pressure is assumed to be about one hundred kilopascals, an absolute reading close to that value reflects the different reference. It does not indicate a damaged zero point. This value is for illustration only and must not be treated as a universal conversion constant.
First establish the process objective: does the system control the remaining absolute pressure in the vessel or the pressure above the surroundings? Then confirm the sensor version and the program against that reference. The sales team should request the full original nameplate and a written description of the expected reading under one known condition. This is usually more effective at identifying an incorrect reference than asking for the desired pressure value alone.